Parameter set 0
Parameters
Controller BUS 6 T
75
Baumüller Nürnberg GmbH
5.94017.06
Parameter overview
ID no.
Name
Range
min. ... max.
Unit
Standard
value
Display
only
velocity and ramp function generator
36
set velocity value
-12000.0000 ... 12000.0000
rpm
0
(
)
43
polarity of set velocity value
0
38
positive velocity limit value
0.0000 ... 12000.0000
rpm
39
negative velocity limit value
0.0000 ... 12000.0000
rpm
91
bipolar velocity limit value
0.0000 ... 12000.0000
rpm
40
actual velocity value
-12000.0000 ... 12000.0000
rpm
32825
ramp function generator
0 ... 1
0
32826
ramp-up time
0.010 ... 60.000
s
0.01
32827
ramp-down time
0.010 ... 60.000
s
0.01
Parameter description
set velocity value
Set velocity value which can be set via the service PC. Switching of set value via
ID no. 32818.
Clockwise rotation of the motor shaft (seen from the front) takes place if the set velocity
value and the polarity are positive.
In the case of analog set value input this parameter serves for display purposes only.
Analog set value input (I/O option board 3.9211)
- MSP
(-10 V .. + 10 V)
at X2:2 and X2:1
- C axis
(-10 V .. + 10 V)
at X2:5 and X2:4
- additional n
set
(-10 V .. + 10 V)
at X3:2 and X3:1
polarity of set velocity value
This parameter corrects the polarity of the set/actual velocity value. Clockwise rotation of
the motor shaft (seen from the front) takes place if the set velocity value and the polarity are
positive.
Bit no.
Meaning
0
set velocity value
0: positive polarity
1: negative polarity
1 ... 2
reserved
3
analog actual velocity value
0: unipolar (clockwise and anti-clockwise speed [0 ... +10V]
1: bipolar
(clockwise speed [0 ... +10V]
anti-clockwise speed [0 ... -10V])
on PCB 3.9211 between X3:4 and X3:6
4 ... 15
reserved
Summary of Contents for BUS 6-T Series
Page 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...