Status messages
Maintenance
Controller BUS 6 T
101
Baumüller Nürnberg GmbH
5.94017.06
8.2.1 Error messages
Parameter overview
ID no.
Name
Range
min. ... max.
Unit
Standard
value
Display
only
error messages
11
Class 1 Diagnostics
129
Manufacturer Class 1 Diagnostics
99
command "reset Class 1 Diagnostics"
32906
BUS operating error
32907
BUS hardware error
32908
BUS software error
32909
initialisation error of BUS I/O
components
32910
supply operating error
32911
BUG hardware error
32785
error init
32786
error IO
Parameter description
Class 1 Diagnostics
Display of drive interlocking. A Class 1 Diagnostics error situation detected by the drive
leads to:
•
controller inhibit with brake down or pulse inhibit
•
output X3:25 switches to high.
•
setting of error bit.
Delete the error bit (after remedying the fault) with the reset command (ID no. 99).
When switching on again a reset signal is automatically generated.
Bit no.
Meaning
0
always 0
1
1: amplifier shutdown temperature exceeded (CI)
2
1: motor shutdown temperature exceeded (CI)
3
1: cooling error shutdown temperature exceeded (CI)
4
1: control voltage error (PI)
5
reserved
6
1: error in electronic commutation system (PI)
7
1: excess current (PI)
8
1: overvoltage (PI)
9 ... 14
reserved
15
1: bit set in Manufacturer Class 1 Diagnostics
PI (pulse inhibit)
CI (controller inhibit)
Summary of Contents for BUS 6-T Series
Page 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...