Installation
Connector pin assignment
30
Controller BUS 6 T
5.94017.06
Baumüller Nürnberg GmbH
Parameter set selection:
Input 3 (S2)
Input 4 (S1)
Parameter set
Low
Low
0
Low
High
1
High
Low
2
High
High
3
Reset:
*
Reset activ if +24 V edge
This input corresponds with its function the command reset error status class 1 (ID no. 99).
If this input is enabled, the output X3:25 (error status class 1) at the same time is high and the LED
„Error“ lights. The „ready for use“ LED goes out and the relay output X3:7/8 is opened (not ready
for use). This reset action lasts approximately 4 s.
a)
The controller´s status is „error“ if it is switched on. When the internal check was successfully,
the ready for use signal is given.
b)
If there is no error and the reset signal is given, the controller´s status changed to „error“ and
when the internal check was successfully the ready for use signal is given again.