2.6.5 Setting of electrical proportional valve (option)
Introduction
The electrical proportional valve is available as an option.
The output pressure from the proportional valve is set by a voltage input signal, 0
- 10 VDC.
The output pressure range is 0.005 - 0.9 MPa.
I/O configuration
The following has to be done in order to configure the system to automatically feed
the electrical proportional valve with 24 V only, when there is a sufficient air pressure
indicated by the air pressure switch. If there is not enough pressure, the electrical
proportional valve works continuously and the lifetime may be shortened.
The related input and output is
gx_air_ok
and
gx_epvalve_on
, where x represents
the actual gun. The example below shows the setting for gun 1.
Note
Action
Create a digital output signal named
g1_epvalve_on
on unit
SWBOARD1
and unit mapping
14
.
1
Create a cross connection between
g1_air_ok
and
g1_epvalve_on
.
2
Setting
Normally the pre-set values are used. But if other settings are desired, do as
described below.
The procedure below details how to set the proportional valve.
Note
Action
Mode
Make sure that the 12-24 VDC power
is connected.
1
Preparation
The keys are locked after
the power is turned on and
cannot be operated.
Loc
is
indicated on LED when the
keys are pushed.
The indication
Loc
flashes on LED by
pushing the DOWN key for two
seconds or more.
The key locking function is released
by pushing the SET key here.
2
Release key lock-
ing
F_1
is indicated on LED.
Press the SET key.
3
Min. pressure
setting
The min. pressure is equal
to 0 VDC input signal.
Set the required min. pressure by us-
ing the UP and DOWN keys.
4
F_2
is indicated on LED.
When finished, press the SET key.
5
The max. pressure is equal
to 10 VDC input signal.
Set the required max. pressure by us-
ing the UP and DOWN keys.
6
Max. pressure
setting
P_1
is indicated on LED.
When finished press the SET key.
7
Continues on next page
192
Product manual - DressPack/SpotPack IRB 6640
3HAC028638-001 Revision: K
© Copyright 2007-2018 ABB. All rights reserved.
2 Installation
2.6.5 Setting of electrical proportional valve (option)
Summary of Contents for DressPack IRB 6640
Page 1: ...ROBOTICS Product manual DressPack SpotPack IRB 6640 ...
Page 8: ...This page is intentionally left blank ...
Page 18: ...This page is intentionally left blank ...
Page 44: ...This page is intentionally left blank ...
Page 194: ...This page is intentionally left blank ...
Page 220: ...This page is intentionally left blank ...
Page 324: ...This page is intentionally left blank ...
Page 338: ...This page is intentionally left blank ...
Page 364: ...This page is intentionally left blank ...
Page 366: ...This page is intentionally left blank ...
Page 369: ......