4.6.3
SS1 acceptance test
Precondition
The converter is ready for operation.
● The converter signals neither faults nor alarms of the safety functions (r0945[0…7],
r2122[0…7]).
● SS1 is not active (r9734.1 = 0).
Procedure
To perform the acceptance test of the SS1 Basic Function, proceed as follows:
Switch on motor
1. Enter a speed setpoint ≠ 0.
2. Switch on the motor (ON command).
3. Check that the correct motor is running.
Select SS1
1. Select SS1 while the motor is switched on.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
2. In your machine, check the following:
– The motor brakes on the OFF3 ramp.
– SS1 is active (r9734.1 = 1).
– After the p9652 time has expired, the converter signals: "STO is active" (r9734.0 = 1).
Deselect SS1
1. Deselect SS1.
2. Check the following:
– SS1 is not active (r9734.1 = 0).
– The converter signals neither faults nor alarms of the safety functions (r0945[0…7],
r2122[0…7]).
Safety functions integrated in the drive
4.6 Acceptance - completion of commissioning
SINAMICS S210 servo drive system
80
Operating Instructions, 12/2017, A5E41702836B AA
Содержание SIMOTICS S-1FK2
Страница 2: ......
Страница 12: ...Table of contents SINAMICS S210 servo drive system 10 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 226: ...Ordering data 11 5 Spare parts SINAMICS S210 servo drive system 224 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 292: ...Parameters 12 2 List of parameters SINAMICS S210 servo drive system 290 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 766: ...Index SINAMICS S210 servo drive system 764 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 767: ......