Note
The higher the set P gain, the faster and more unstable the control.
p1462[0]
Speed controller integral time
Changeable: T, U
Data type: FloatingPoint32
P group: Closed-loop control
Min: 0.00 [ms]
Max: 100000.00 [ms]
Def: 20.00 [ms]
Description:
Sets the integral time for the speed controller
The drive determines the integral time for One Button Tuning - and writes the value to p1462.
Dependency:
See also: p1460
Note
The shorter the integral time, the faster and more unstable the control.
p1498[0]
Load moment of inertia
Changeable: T, U
Data type: FloatingPoint32
P group: Closed-loop control
Min: - [kgm²]
Max: - [kgm²]
Def: - [kgm²]
Description:
Sets the load moment of inertia.
The setting is made during commissioning while the One Button Tuning is being performed.
p1520[0]
Torque limit motoring
Changeable: T, U
Data type: FloatingPoint32
P group: Closed-loop control
Scaling: p2003
Min: -1000000.00 [Nm]
Max: 20000000.00 [Nm]
Def: 0.00 [Nm]
Description:
Sets the torque limit value when motoring.
This setting is made as part of the basic commissioning.
Dependency:
See also: p1521, p1532, r1538, r1539
p1521[0]
Torque limit regenerating
Changeable: T, U
Data type: FloatingPoint32
P group: Closed-loop control
Scaling: p2003
Min: -20000000.00 [Nm]
Max: 1000000.00 [Nm]
Def: 0.00 [Nm]
Description:
Setting the regenerative torque limit
This setting is made as part of the basic commissioning.
Dependency:
See also: p1520, p1532, r1538, r1539
p1532[0]
Torque limit offset
Changeable: T, U
Data type: FloatingPoint32
P group: Closed-loop control
Scaling: p2003
Min: -100000.00 [Nm]
Max: 100000.00 [Nm]
Def: 0.00 [Nm]
Description:
Sets the offset for the torque limit.
The setting allows electronic weight equalization to be used for vertical axes.
Parameters p1520 and p1521 are offset by the set value in the same direction.
Dependency:
See also: p1520, p1521
r1538
Torque limit motoring active
Data type: FloatingPoint32
P group: Closed-loop control
Scaling: p2003
Description:
Displays the currently active torque limit when motoring.
Note
The value in p1538 may not exceed the value in p1521.
Parameters
12.2 List of parameters
SINAMICS S210 servo drive system
246
Operating Instructions, 12/2017, A5E41702836B AA
Содержание SIMOTICS S-1FK2
Страница 2: ......
Страница 12: ...Table of contents SINAMICS S210 servo drive system 10 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 226: ...Ordering data 11 5 Spare parts SINAMICS S210 servo drive system 224 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 292: ...Parameters 12 2 List of parameters SINAMICS S210 servo drive system 290 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 766: ...Index SINAMICS S210 servo drive system 764 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 767: ......