![Siemens SIMOTICS S-1FK2 Скачать руководство пользователя страница 723](http://html.mh-extra.com/html/siemens/simotics-s-1fk2/simotics-s-1fk2_operating-instructions-manual_379045723.webp)
F37851
HF Damping Module (CU): Sign-of-life missing
Message value:
Component number: %1, fault cause: %2
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from the HF Damping Module to the Control Unit.
The DRIVE-CLiQ component did not set the sign-of-life to the Control Unit.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
Upgrade the firmware of the component involved.
Note:
HF Damping Module
F37860
HF Damping Module (CU): Telegram error
Message value:
Component number: %1, fault cause: %2
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
721
Содержание SIMOTICS S-1FK2
Страница 2: ......
Страница 12: ...Table of contents SINAMICS S210 servo drive system 10 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 226: ...Ordering data 11 5 Spare parts SINAMICS S210 servo drive system 224 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 292: ...Parameters 12 2 List of parameters SINAMICS S210 servo drive system 290 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 766: ...Index SINAMICS S210 servo drive system 764 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 767: ......