r1196
DSC position setpoint
Data type: Integer32
P group: Encoder
Description:
Displays the position setpoint of Dynamic Servo Control in fine pulses.
Note
DSC: Dynamic Servo Control
p1215
Motor holding brake configuration
Changeable: T
Data type: Integer16
P group: Functions
Min: 0
Max: 2
Def: 0
Description:
Sets the configuration for the motor holding brake.
Re value 2:
This setting allows the motor shaft to be rotated for installation purposes.
Value:
0:
No motor holding brake available
1:
Motor holding brake acc. to sequence control
2:
Motor holding brake always open
Dependency:
See also: p1216, r1216, p1217, r1217, p1226, p1227, p1228
CAUTION
For the setting p1215 = 0, if a brake is used, it remains closed. If the motor moves, this will destroy the brake.
Setting p1215 = 2 is not permissible if the brake is used to hold loads.
r1216
Motor holding brake opening time
Data type: FloatingPoint32
P group: Functions
Description:
Displays the opening time for the motor holding brake.
The speed setpoint is kept at 0 for this time. The speed setpoint is then enabled.
Recommendation:
This time should be set longer than the actual opening time of the brake. This ensures that the drive cannot accelerate
when the brake is applied.
Dependency:
See also: p1215, p1217, r1217
Note
For p1216 = 0 ms, the monitoring and the message A07931 "Brake does not open" are deactivated.
r1217
Motor holding brake closing time
Data type: FloatingPoint32
P group: Functions
Description:
Displays the time to close the motor holding brake.
If the drive signals that the motor is at a standstill, if the holding brake is activated, after the closing time has expired,
the pulses are canceled. This prevents the load from sagging, for example.
Recommendation:
This time should be set longer than the actual closing time of the brake. This ensures that the pulses are only
suppressed after the brake has closed.
Dependency:
See also: p1215, p1216, r1216
NOTICE
If the selected closing time is too short with respect to the actual closing time of the brake, then the load can sag.
If the closing time is selected to be too long with respect to the actual closing time of the brake, the control works
against the brake and therefore reduces its lifetime.
Note
For p1217 = 0 ms, the monitoring and the message A07932 "Brake does not close" are deactivated.
p1226[0]
Threshold for zero speed detection
Changeable: T, U
Data type: FloatingPoint32
P group: Functions
Min: 0.00 [rpm]
Max: 210000.00 [rpm]
Def: 20.00 [rpm]
Parameters
12.2 List of parameters
SINAMICS S210 servo drive system
244
Operating Instructions, 12/2017, A5E41702836B AA
Содержание SIMOTICS S-1FK2
Страница 2: ......
Страница 12: ...Table of contents SINAMICS S210 servo drive system 10 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 226: ...Ordering data 11 5 Spare parts SINAMICS S210 servo drive system 224 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 292: ...Parameters 12 2 List of parameters SINAMICS S210 servo drive system 290 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 766: ...Index SINAMICS S210 servo drive system 764 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 767: ......