F07082
Macro: Execution not possible
Message value:
Fault cause: %1, supplementary information: %2, preliminary parameter number: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The macro cannot be executed.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex:
cccc = preliminary parameter number, bb = supplementary information, aa = fault cause
Fault causes for the trigger parameter itself:
19: Called file is not valid for the trigger parameter.
20: Called file is not valid for parameter 15.
21: Called file is not valid for parameter 700.
22: Called file is not valid for parameter 1000.
23: Called file is not valid for parameter 1500.
24: Data type of a TAG is incorrect (e.g. Index, number or bit is not U16).
Fault causes for the parameters to be set:
25: Error level has an undefined value.
26: Mode has an undefined value.
27: A value was entered as string in the tag value that is not "DEFAULT".
31: Entered drive object type unknown.
32: A device was not able to be found for the determined drive object number.
34: A trigger parameter was recursively called.
35: It is not permissible to write to the parameter via macro.
36: Check, writing to a parameter unsuccessful, parameter can only be read, not available, incorrect data type, value range
or assignment incorrect.
37: Source parameter for a BICO interconnection was not able to be determined.
38: An index was set for a non-indexed (or CDS-dependent) parameter.
39: No index was set for an indexed parameter.
41: A bit operation is only permissible for parameters with the parameter format DISPLAY_BIN.
42: A value not equal to 0 or 1 was set for a BitOperation.
43: Reading the parameter to be changed by the BitOperation was unsuccessful.
51: Factory setting for DEVICE may only be executed on the DEVICE.
61: The setting of a value was unsuccessful.
Remedy:
- check the parameter involved.
- check the macro file and BICO interconnection.
F07083
Macro: ACX file not found
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The ACX file (macro) to be executed was not able to be found in the appropriate directory.
Fault value (r0949, interpret decimal):
Parameter number with which the execution was started.
Remedy:
- check whether the file is saved in the appropriate directory on the memory card.
Example:
If p0015 is set to 1501, then the selected ACX file must be located in the following directory:
... /PMACROS/DEVICE/P15/PM001501.ACX
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
428
Operating Instructions, 12/2017, A5E41702836B AA
Содержание SIMOTICS S-1FK2
Страница 2: ......
Страница 12: ...Table of contents SINAMICS S210 servo drive system 10 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 226: ...Ordering data 11 5 Spare parts SINAMICS S210 servo drive system 224 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 292: ...Parameters 12 2 List of parameters SINAMICS S210 servo drive system 290 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 766: ...Index SINAMICS S210 servo drive system 764 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 767: ......