Cause:
The utilization for a data memory area is too large.
Fault value (r0949, interpret binary):
Bit 0 = 1: High-speed data memory 1 overloaded
Bit 1 = 1: High-speed data memory 2 overloaded
Bit 2 = 1: High-speed data memory 3 overloaded
Bit 3 = 1: High-speed data memory 4 overloaded
Remedy:
- deactivate the function module.
- deactivate drive object.
- remove the drive object from the target topology.
A01069
Parameter backup and device incompatible
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter backup on the memory card and the drive unit do not match.
The module boots with the factory settings.
Example:
Devices A and B. are not compatible and a memory card with the parameter backup for device A is inserted in device B.
Remedy:
- insert a memory card with compatible parameter backup and carry out a POWER ON.
- insert a memory card without parameter backup and carry out a POWER ON.
- save the parameters (p0977 = 1).
F01072
Memory card restored from the backup copy
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The Control Unit was switched-off while writing to the memory card. This is why the visible partition became defective.
After switching on, the data from the non-visible partition (backup copy) were written to the visible partition.
Remedy:
Check that the firmware and parameterization is up-to-date.
A01073 (N)
POWER ON required for backup copy on memory card
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter assignment on the visible partition of the memory card has changed.
In order that the backup copy on the memory card is updated on the non-visible partition, it is necessary to carry out a
POWER ON or hardware reset (p0972) of the Control Unit.
Note:
It is possible that a new POWER ON is requested via this alarm (e.g. after saving with p0971 = 1).
Remedy:
- carry out a POWER ON (switch-off/switch-on) for the Control Unit.
- carry out a hardware reset (RESET button, p0972).
Reaction upon N: NONE
Acknowl. upon N: NONE
F01082
Parameter error when powering up from data backup
Message value:
Parameter: %1, Index: %2, fault cause: %3
Drive object:
All objects
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
308
Operating Instructions, 12/2017, A5E41702836B AA
Содержание SIMOTICS S-1FK2
Страница 2: ......
Страница 12: ...Table of contents SINAMICS S210 servo drive system 10 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 226: ...Ordering data 11 5 Spare parts SINAMICS S210 servo drive system 224 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 292: ...Parameters 12 2 List of parameters SINAMICS S210 servo drive system 290 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 766: ...Index SINAMICS S210 servo drive system 764 Operating Instructions 12 2017 A5E41702836B AA ...
Страница 767: ......