Chapter 7: Using the Command Line Interface
329
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
Note: If the requested sensor type is not supported, the message "Not
available" is displayed.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the lower critical threshold for the
specified inlet pole sensor.
disable
Disables the lower critical threshold for the
specified inlet pole sensor.
A numeric value Sets a value for the lower critical threshold of the
specified inlet pole sensor and enables this
threshold at the same time.
Example
The following command enables the Lower Critical threshold for the pole 2
(L2-L3) voltage of the inlet 1.
config:#
sensor inletpole 1 L2 voltage lowerCritical enable
Setting the Lower Warning Threshold for an Inlet Pole
This command syntax configures the Lower Warning threshold of an inlet
pole.