Chapter 7: Using the Command Line Interface
334
Option
Description
disable
Disables the upper critical threshold for the
specified circuit breaker sensor.
A numeric value Sets a value for the upper critical threshold of the
specified circuit breaker sensor and enables this
threshold at the same time.
Example
The following command sets the Upper Critical threshold for the 3rd circuit
breaker to 16A. It also enables the upper critical threshold if this threshold
has not been enabled yet.
config:#
sensor ocp 3 current upperCritical 16
Setting the Upper Warning Threshold for a Circuit Breaker
This command syntax configures the Upper Warning threshold of a circuit
breaker.
config:#
sensor ocp <n> <sensor type> upperWarning <option>
Variables:
<n> is the number of the circuit breaker that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
Note: If the requested sensor type is not supported, the message "Not
available" is displayed.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the upper warning threshold for the
specified circuit breaker sensor.
disable
Disables the upper warning threshold for the
specified circuit breaker sensor.
A numeric value Sets a value for the upper warning threshold of the
specified circuit breaker sensor and enables this
threshold at the same time.