![Raritan PX-1000 Series Скачать руководство пользователя страница 153](http://html1.mh-extra.com/html/raritan/px-1000-series/px-1000-series_user-manual_3768194153.webp)
Chapter 5: Using the Web Interface
138
last known: Restores all outlets to their previous power states
before the Dominion PX device was powered off.
4. Click OK to save the changes.
Setting the Outlet-Specific Default State
This section only applies to outlet-switching capable PDUs.
By default, the power state of each outlet follows the PDU-defined setting.
Setting the default state of a particular outlet to a value other than "PDU
defined" overrides the PDU-defined setting on that outlet.
To set the default power state for a specific outlet:
1. If the Outlets folder is not expanded, expand it to show all outlets. See
Expanding the Tree
(on page 71).
2. Click the outlet you want in the Dominion PX Explorer pane. The page
specific to that outlet opens in the right pane.
3. Click Setup in the Settings section. The setup dialog for the selected
outlet appears.
Tip: When the Outlets folder is selected, you can also trigger the same
dialog by highlighting the outlet on the Outlets page and then clicking
Setup.
4. In the "State on device startup" field, click the drop-down arrow and
select an option from the list.
on: Turns on this outlet when the Dominion PX device powers up.
off: Turns off this outlet when the Dominion PX device powers up.
last known: Restores this outlet to the previous power state before
the Dominion PX device was powered off.
PDU defined: The outlet's default power state is determined by the
PDU-defined state. See
Setting the PDU-Defined Default State
(on page 137)
Tip: The information in parentheses following the option "PDU
defined" indicates the current PDU-defined selection.
5. Click OK to save the changes.
Содержание PX-1000 Series