Chapter 7: Using the Command Line Interface
340
Option
Description
disable
Disables the upper warning threshold for the
specified environmental sensor.
A numeric value Sets a value for the upper warning threshold of the
specified environmental sensor and enables this
threshold at the same time.
Example
The following command enables the Upper Warning threshold of the
environmental "temperature" sensor with the ID number 4.
config:#
sensor externalsensor 4 temperature upperWarning enable
Setting the Sensor's Lower Critical Threshold
This command syntax configures the Lower Critical threshold of a numeric
environmental sensor.
config:#
sensor externalsensor <n> <sensor type> lowerCritical <option>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is assigned and shown in the Dominion PX
web interface. It is an integer between 1 and 16.
<sensor type> is one of these sensor types:
temperature,
humidity,
airPressure or air Flow
.
Note: If the specified sensor type does not match the type of the
specified environmental sensor, this error message appears:
"Specified sensor type 'XXX' does not match the sensor's type
(<sensortype>)," where XXX is the specified sensor type, and
<sensortype> is the correct sensor type.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the lower critical threshold for the
specified environmental sensor.
disable
Disables the lower critical threshold for the
specified environmental sensor.
A numeric value Sets a value for the lower critical threshold of the
specified environmental sensor and enables this
threshold at the same time.