Chapter 5: Using the Web Interface
141
Setting the Initialization Delay
This section only applies to outlet-switching capable PDUs.
The outlet initialization delay determines how long the Dominion PX
device waits before providing power to all outlets during power cycling or
after recovering from a temporary power loss. This is useful in cases
where power may not initially be stable after being restored, or when UPS
batteries may be charging.
To set the initialization delay for all outlets:
1. Click the PDU folder.
Note: The PDU folder is named "my PX" by default. The name
changes after customizing the device name. See
Naming the PDU
(on page 83).
2. Click Setup in the Settings section. The Pdu Setup dialog appears.
3. In the "Outlet initialization delay on device startup" field, click the
drop-down arrow and select an option from the list. Valid range is 1
second to 1 hour.
Time units in the list are explained below:
s:
second(s)
min:
minute(s)
h:
hour(s)
4. Click OK to save the changes.
Tip: When there are a large number of outlets, set the value to a lower
number so that you can avoid a long wait before all the outlets are
available again.