Chapter 5: Using the Web Interface
177
2. Select "Inlet I1" from the submenu because that is the inlet in
question.
3. Select "Sensor" to refer to sensor readings.
4. Select "Any sub-event" because we want to specify all events related
to all types of inlet sensors and thresholds, such as current, voltage,
upper critical threshold, upper warning threshold, lower critical
threshold, lower warning threshold, and so on.
5. Select "System SNMP Trap Action" to send SNMP traps to respond to
the specified event.
6. Select the "both" radio button so that the SNMP traps are sent both
when any sensor reading of Inlet I1 moves past any threshold into the
warning or critical range and when the sensor reading returns to
normal.
For example, when the Inlet I1's voltage crosses into the upper
warning range, the SNMP traps are sent, and when the voltage drops
below the upper warning threshold, the SNMP traps are sent again.
Sample Environmental-Sensor-Level Event Rule
This section only applies to outlet-switching capable PDUs.
In this example, we want Dominion PX to enable the load shedding
function when a contact closure sensor enters the alarmed state. This
sample event rule requires the creation of a new action before creating the
rule.
Step 1: create a new action for enabling the load shedding mode
1. Choose Device Settings > Event Rules. The Event Rule Settings
dialog appears.
2. Click the Actions tab.
3. Click New Action.
4. In the Action Name field, type a name to identify this action. In this
illustration, type Enable Load Shedding.
5. In the Action field, select "Change load shedding state."
6. In the Operation field, select "Enable load shedding."
7. Click Save to save this action.