Appendix E: Integration
406
Note: PDU discovery is complete once the PDU model type is determined.
SNMP fields such as contact or location values are not determined until
this device is polled for the first time.
Once added, the PDU appears in the PDU list. Power IQ begins
polling the PDU for sensor data. You can configure how often Power
IQ polls PDU. See Configuring Polling Intervals in the Power IQ User
Guide.
Dominion KX II Configuration
PX2 series PDUs can be connected to the Raritan's Dominion KX II device
(a digital KVM switch) to provide one more alternative of power control.
Note that this integration requires the following firmware versions:
Dominion KX II -- 2.4 or later
PX2 series -- 2.2 or later
Dominion KX II integration requires D2CIM-PWR and straight CAT5 cable.
For more information on Dominion KX II, see either of the following:
Dominion KX II User Guide: Available on the Raritan website's
Firmware and Documentation section
(
http://www.raritan.com/support/firmware-and-documentation/
).
Dominion KX II Online Help: Available on the
Product Online Help
section
(
http://www.raritan.com/support/online-help/
).
Configuring Rack PDU (Power Strip) Targets
The KX II allows you to connect rack PDUs (power strips) to KX II ports.
KX II rack PDU configuration is done from the KX II Port Configuration
page.
Connecting a Rack PDU
Rack PDUs are connected to the KX II using the D2CIM-PWR CIM.
To connect the rack PDU:
1. Connect the male RJ-45 of the D2CIM-PWR to the female RJ-45
connector labeled "FEATURE" of the rack PDU.
2. Connect the female RJ-45 connector of the D2CIM-PWR to any of the
available female system port connectors on the KX II using a straight
through Cat5 cable.
3. Attach an AC power cord to the target server and an available rack
PDU outlet.
4. Connect the rack PDU to an AC power source.
Содержание PX-1000 Series