Chapter 5: Using the Web Interface
189
Tip: The information in parentheses following each ID number
indicates whether the number has been assigned to any sensor. If it
has been assigned to a sensor, it shows that sensor's serial number.
Otherwise, it shows the term "unused."
6. Click OK. The Dominion PX starts to track and display the managed
sensor's reading and/or state.
7. To manage additional sensors, repeat Steps 3 to 6.
Note: When the number of managed sensors reaches the maximum, you
CANNOT manage additional sensors until you remove or replace any
managed sensors. To remove a sensor, see
Unmanaging
Environmental Sensors
(on page 195).
Configuring Environmental Sensors
You may change the default name for easily identifying the managed
sensor, and describe its location with X, Y and Z coordinates.
To configure environmental sensors:
1. If the PDU folder is not expanded, expand it to show all components
and component groups. See
Expanding the Tree
(on page 71).
Note: The PDU folder is named "my PX" by default. The name
changes after customizing the device name. See
Naming the PDU
(on page 83).
2. Click External Sensors in the Dominion PX Explorer pane, and the
External Sensors page opens in the right pane.
3. Select the sensor that you want to configure.
4. Click Setup. The "Setup of external sensor <serial number> (<sensor
type>)" dialog appears, where <serial number> is the serial number of
this sensor and <sensor type> is the sensor's type.
Tip: You can also trigger the same setup dialog by selecting the
desired environmental sensor icon in the tree and then clicking Setup
on that sensor's page opened in the right pane.
5. If the selected environmental sensor is the Raritan contact closure
sensor connected with a third-party detector/switch, select the
appropriate sensor type in the Binary Sensor Subtype field.
Contact: The detector/switch is designed to detect the door lock or
door open/closed status.
Smoke Detection: The detector/switch is designed to detect the
appearance of smoke.
Water Detection: The detector/switch is designed to detect the
appearance of water on the floor.