Chapter 7: Using the Command Line Interface
260
For more information, see
Setting Data Logging
(on page 99).
Example
The following command enables the data logging feature.
config:#
pdu dataRetrieval enable
Setting the Data Logging Measurements Per Entry
This command syntax defines the number of measurements accumulated
per log entry.
config:#
pdu measurementsPerLogEntry <number>
Variables:
<number> is an integer between 1 and 600. The default is 60 samples
per log entry.
For more information, see
Setting Data Logging
(on page 99).
Example
The following command determines that 66 measurements are
accumulated per log entry for sensors, that is, 66 seconds.
config:#
pdu measurementsPerLogEntry 66
Specifying the Device Altitude
This command syntax specifies your Dominion PX device's altitude above
sea level (in meters). You must specify the Dominion PX device's altitude
above sea level if a Raritan differential air pressure sensor is attached.
This is because the device's altitude is associated with the altitude
correction factor. See
Altitude Correction Factors
(on page 414).
config:#
pdu deviceAltitude <altitude>
Variables:
<altitude> is an integer between 1 and 3000 meters.