Chapter 7: Using the Command Line Interface
337
Setting the Circuit Breaker's Deassertion Hysteresis
This command syntax configures the deassertion hysteresis value of a
circuit breaker.
config:#
sensor ocp <n> <sensor type> hysteresis <value>
Variables:
<n> is the number of the circuit breaker that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
Note: If the requested sensor type is not supported, the message "Not
available" is displayed.
<value> is a numeric value that is assigned to the hysteresis of the
specified circuit breaker sensor. See
What is Deassertion
Hysteresis?
(on page 153) for the function of the deassertion
hysteresis.
Example
The following command sets the deassertion hysteresis of the RMS
current of the 3rd circuit breaker to 0.2A. That is, the current must drop by
at least 0.2A below the upper threshold or rise by at least 0.2A above the
lower threshold before any threshold-crossing event is deasserted.
config:#
sensor ocp 3 current hysteresis 0.2
Setting the Circuit Breaker's Assertion Timeout
This command syntax configures the assertion timeout value of a circuit
breaker.
config:#
sensor ocp <n> <sensor type> assertionTimeout <value>
Variables:
<n> is the number of the circuit breaker that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor