![Raritan PX-1000 Series Скачать руководство пользователя страница 154](http://html1.mh-extra.com/html/raritan/px-1000-series/px-1000-series_user-manual_3768194154.webp)
Chapter 5: Using the Web Interface
139
Changing the Cycling Power-Off Period
This section only applies to outlet-switching capable PDUs.
Power cycling the outlet(s) turns the outlet(s) off and then back on. You
can adjust the length of the time it takes for the outlets to turn back on after
they are switched OFF during the power cycle.
The power-off period of power cycle can be set for all outlets or for an
individual outlet. Note that the value set for an individual outlet always
overrides the value set for all outlets.
Changing the PDU-Defined Cycling Power-Off Period
This section only applies to outlet-switching capable PDUs.
The "PDU-defined" power-off period determines how long it takes for all
outlets to turn on after they are turned OFF during the power cycle. The
default PDU-defined power-off period is 10 seconds (10 s).
Note: To set a different power-off period on a particular outlet, see
Changing the Outlet-Specific Cycling Power-Off Period
(on page
140).
To set the power-off period for all outlets:
1. Click the PDU folder.
Note: The PDU folder is named "my PX" by default. The name
changes after customizing the device name. See
Naming the PDU
(on page 83).
2. Click Setup in the Settings section. The Pdu Setup dialog appears.
3. In the "Power off period during power cycle" field, click the drop-down
arrow and select an option from the list. Valid range is zero second to
one hour.
Time units in the list are explained below:
s:
second(s)
min:
minute(s)
h:
hour(s)
You can also type a value if the desired time is not listed. For example,
type "15 s" if you want a 15-second delay.
4. Click OK to save the changes.
Содержание PX-1000 Series
Страница 423: ...Appendix E Integration 408 3 Click OK ...