Connection Notes
The following diagram illustrates the connection of analog current sensors to the analogue
current inputs of PiXtend V2 -L-.
The measuring current flows through a shunt resistor with a value of 20 Ω. So if a voltage
sensor is connected to the output, the maximum permissible measuring current of 20 mA
flows even at very low voltages:
Umax = 20 Ω * 20 mA = 0.4 V
www.pixtend.com
Copyright by Qube Solutions GmbH
119 / 146
Figure 74: Principle circuit diagram: Connection of analog current inputs