Wire Size
FIRE HAZARD To satisfy safety requirements, load wires must be large enough not to
overheat when carrying the maximum short-circuit output current. If there is more than
one load, then any pair of load wires must be capable of safely carrying the full-rated
current of the unit. Paralleled load wires may be required for larger-ampacity models.
The following table lists the characteristics of AWG (American Wire Gauge) copper wire.
AWG
Equivalent mm2
Nearest Metric size
Ampacity (Note 1)
Resistance (Note 2)
18
0.82
1.0 mm2
up to 14 A
6.385 Ω
16
1.31
1.5 mm2
up to 18 A
4.016 Ω
14
2.1
2.5 mm2
up to 25 A
2.525 Ω
12
3.3
4 mm2
up to 30 A
1.588 Ω
10
5.3
6 mm2
up to 40 A
0.999 Ω
8
8.4
10 mm2
up to 60 A
0.628 Ω
6
13.3
16 mm2
up to 80 A
0.395 Ω
4
21.2
25 mm2
up to 105 A
0.248 Ω
2
33.6
35 mm2
up to 140 A
0.156 Ω
1/0
53.5
50 mm2
up to 195 A
0.098 Ω
2/0
67.4
70 mm2
up to 225 A
0.078 Ω
3/0
85
95 mm2
up to 260 A
0.062 Ω
4/0
107
120 mm2
up to 300 A
0.049 Ω
6.2/0 (350 MCM)
177
185 mm2
up to 420 A
N/A
Note 1 Ampacity is based on a single conductor in free air, 26-30 °C ambient temperature with the conductor rated at 60 °C. Ampacity
decreases at higher temperatures.
Note 2 Resistance is in ohms/1000 feet, at 20 °C wire temperature.
Along with ampacity, you must also consider voltage drop in the load lead due to wire resistance
sizing wires. The power supply will tolerate a voltage drop of 1 V per lead while maintaining the
specified programming accuracy, measurement accuracy, and load regulation (see
).
Voltage drops of up to 25% of the rated output voltage per lead will be tolerated - resulting in an
additional 4 mV of voltage regulation for each additional volt dropped per load lead. Of course, any
voltage drop in the load leads reduces the maximum voltage available at the load. Subtract the load
lead drop from the rated output voltage to determine the maximum voltage available at the load.
Single Load Connections
1. As shown in the following figure, terminate all load wires with wire terminal lugs securely
attached. DO NOT use unterminated wires for load connections at the power supply.
Keysight N69100 Series Operating and Service Guide
63
2 Installing the Instrument
Содержание N69100 Series
Страница 1: ...Keysight Advanced Power System DC Power Supply N69100 Series Operating and Service Guide...
Страница 2: ......
Страница 14: ......
Страница 50: ...Outline Diagram for 10 kW Models 1 Quick Reference 50 Keysight N69100 Series Operating and Service Guide...
Страница 51: ...Outline Diagram for 20 kW Models Keysight N69100 Series Operating and Service Guide 51 1 Quick Reference...
Страница 52: ......
Страница 80: ......
Страница 94: ......
Страница 210: ...Status Diagram 5 SCPI Programming Reference 210 Keysight N69100 Series Operating and Service Guide...
Страница 212: ...Trigger Diagram 5 SCPI Programming Reference 212 Keysight N69100 Series Operating and Service Guide...
Страница 230: ...Models N69172A and N69173A 6 Verification and Calibration 230 Keysight N69100 Series Operating and Service Guide...
Страница 244: ......