![Keysight Technologies N69100 Series Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/keysight-technologies/n69100-series/n69100-series_operating-and-service-manual_1962218041.webp)
Inductive Load Boundary for Constant Current (CC) Operation
The following figures show the boundary limitations for inductive loads with equivalent series
resistance (ESR) for constant current operation. Operation below the marginal stability lines may
result in output instability. Note that lead and DUT resistance and inductance are indistinguishable in
this context. It is also important to consider the voltage drop and power dissipation in the leads from
increased lead resistance. Refer to
for details.
EQUIPMENT DAMAGE The power supply's internal voltage clamps are susceptible to
thermal damage when the output is abruptly turned off at full load current if the lead
inductance exceeds the model-dependent
characteristic.
Inductive Load Boundary (N69172A units)
Inductive Load Boundary (N69173A units)
1. The output is stable in this region
2. The output may overshoot in this region
3. The output may be unstable in this region
Inductive Load Boundary (N69143A units, Comp 0)
Inductive Load Boundary (N69143A units, Comp 1)
Keysight N69100 Series Operating and Service Guide
41
1 Quick Reference
Содержание N69100 Series
Страница 1: ...Keysight Advanced Power System DC Power Supply N69100 Series Operating and Service Guide...
Страница 2: ......
Страница 14: ......
Страница 50: ...Outline Diagram for 10 kW Models 1 Quick Reference 50 Keysight N69100 Series Operating and Service Guide...
Страница 51: ...Outline Diagram for 20 kW Models Keysight N69100 Series Operating and Service Guide 51 1 Quick Reference...
Страница 52: ......
Страница 80: ......
Страница 94: ......
Страница 210: ...Status Diagram 5 SCPI Programming Reference 210 Keysight N69100 Series Operating and Service Guide...
Страница 212: ...Trigger Diagram 5 SCPI Programming Reference 212 Keysight N69100 Series Operating and Service Guide...
Страница 230: ...Models N69172A and N69173A 6 Verification and Calibration 230 Keysight N69100 Series Operating and Service Guide...
Страница 244: ......