causing an electrical shock hazard. Use the procedures for checking
receptacles in
Electrical Safety for IBM Service Representatives
, S229-8124.
2.
When three-phase voltage is used to provide power to the iSeries 400 system,
correct balancing of the load on each phase is important. Each unit in the
iSeries 400 system uses only two of the three phases. Therefore, the units
should be connected so that all three phases are used equally. Use the
following as a guide to help balance the phases:
v
Connect a unit across phases A and B
v
Connect a unit across phases B and C
v
Connect a unit across phases A and C
v
Continue in this sequence for additional units
3.
The power distribution neutral must return to the “separately derived source”
through an insulated wire that is the same size as the phase wire or larger.
Note:
“Separately derived source” is defined in INT-PIP8 Grounding, step 4
on page 335.
4.
The iSeries 400 system and its attached equipment should be the only units
that are connected to the power distribution network that the system gets its
power.
5.
The equipment that is attached to the iSeries 400 system, such as workstations
and printers, must be attached to the power distribution network for the
system when possible.
6.
Each unit in the iSeries 400 system must have a circuit breaker that controls
only the AC voltage to that unit. No other equipment may get its AC voltage
from the same circuit breaker.
7.
Check all circuit breakers in the network that supply AC power to the iSeries
400 system as follows:
v
Ensure that the circuit breakers are installed tightly in the power panel and
are not loose.
v
Feel the front surface of each circuit breaker to detect if it is warm. A warm
circuit breaker may be caused by:
– The circuit breaker that is not installed tightly in the power panel
– The contacts on the circuit breaker that is not making a good electrical
connection with the contacts in the power panel.
– A defective circuit breaker.
– A circuit breaker of a smaller current rating than the current load which
is going through it.
– Devices on the branch circuit which are using more current than their
rating.
8.
Equipment that uses a large amount of current, such as: Air conditioners,
copiers, and FAX machines, should not receive power from the same branch
circuits as the system or its workstations. Also, the wiring that provides AC
voltage for this equipment should not be placed in the same conduit as the
AC voltage wiring for the iSeries 400 system. The reason for this is that this
equipment generates AC noise pulses. These pulses can get into the AC
voltage for the iSeries 400 system and cause intermittent problems.
9.
Measure the AC voltage to each unit to ensure that it is in the normal range.
Is the voltage outside the normal range?
No
Yes
Intermittent PIPs
Chapter 3. Problem Isolation Procedures (PIPs), Failing Items, and Symbolic FRU Isolation
337
Содержание i 830
Страница 1: ...iSeries iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts Version 5 SY44 5969 01...
Страница 2: ......
Страница 3: ...iSeries iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts Version 5 SY44 5969 01...
Страница 14: ...xii iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 15: ...Part 1 Problem Analysis Copyright IBM Corp 2000 2001 1...
Страница 16: ...2 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 628: ...Symbolic FRUs 614 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 629: ...Part 2 FRU Replacement Copyright IBM Corp 2000 2001 615...
Страница 630: ...616 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 817: ...Part Assemblies Chapter 5 Locations Addresses and Part Listings 803...
Страница 822: ...Assembly 2 continued 808 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 824: ...Assembly 2 continued 810 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 826: ...Assembly 2 continued 812 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 830: ...Assembly 3 continued 816 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 832: ...Assembly 3 continued 818 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 834: ...Assembly 3 continued 820 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 836: ...Assembly 3 continued 822 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 844: ...Assembly 6 continued 830 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 848: ...Assembly 7 continued 834 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 850: ...Assembly 7 continued 836 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 858: ...Assembly 10 continued 844 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 860: ...Assembly 10 continued 846 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 862: ...Assembly 10 continued 848 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 864: ...Assembly 10 continued 850 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 870: ...Assembly 12 continued 856 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 872: ...Assembly 12 continued 858 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 874: ...Assembly 12 continued 860 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 876: ...Assembly 12 continued 862 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 882: ...Assembly 14 continued 868 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 888: ...Assembly 16 continued 874 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 894: ...Assembly 19 External Cables External Cables 880 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 897: ...Miscellaneous Chapter 5 Locations Addresses and Part Listings 883...
Страница 898: ...Assembly 20 Miscellaneous Miscellaneous 884 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 906: ...892 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 962: ...948 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 963: ...Part 3 Appendixes Copyright IBM Corp 2000 2001 949...
Страница 964: ...950 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 968: ...954 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 970: ...956 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 974: ...960 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 980: ...966 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 982: ...968 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 984: ...970 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 986: ...972 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 990: ...976 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 999: ......
Страница 1000: ...Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber SY44 5969 01...