2.
For each unit, check continuity from a conductive area on the frame to the
ground pin on the plug. Do this at the end of the mainline AC power cable.
The resistance must be 0.1 ohm or less.
3.
Ground continuity must be present from each unit receptacle to an effective
ground. Therefore, check the following:
v
The AC voltage receptacle for each unit must have a ground wire connected
from the ground terminal on the receptacle to the ground bar in the power
panel.
v
The ground bars in all branch circuit panels must be connected with an
insulated ground wire to a
ground point
, which is defined as follows:
– The nearest available metal cold water pipe, only if the pipe is effectively
grounded to the earth (see
National Electric Code
Section 250-81, in the
United States).
– The nearest available steel beams in the building structure, only if the
beam is effectively grounded to the earth.
– Steel bars in the base of the building or a metal ground ring that is
around the building under the surface of the earth.
– A ground rod in the earth (see
National Electric Code
Section 250-83, in the
United States).
Note:
For installations in the United States only, by National Electrical Code
standard, if more than one of the preceding grounding methods are
used, they must be connected together electrically. See
National Electric
Code
Section 250, for more information on grounding.
v
The grounds of all separately derived sources (uninterruptable power supply,
service entrance transformer, system power module, motor generator) must
be connected to a
ground point
as defined above.
v
The service entrance ground bar must connect to a
ground point
as defined
above.
v
All ground connections
must be tight
.
v
Check continuity of the ground path for each unit that is using an ECOS
tester, Model 1023-100. Check continuity at each unit receptacle, and measure
to the
ground point
as defined above. The total resistance of each ground
path must be 1.0 ohm or less. If you cannot meet this requirement, check for
faults in the ground path.
v
Conduit is sometimes used to meet wiring code requirements. If conduit is
used, the branch circuits must still have a green (or green and yellow) wire
for grounding as stated above.
Note:
The ground bar and the neutral bar must never be connected together
in branch circuit power panels.
The ground bar and the neutral bar in the power panels that make up the
electrical power network for the iSeries 400 system must be connected
together. This applies to the first electrically isolating unit that is found in the
path of electrical wiring from the iSeries 400 system to the service entrance
power panel. This isolating unit is sometimes referred to as a
separately
derived source
. It can be an uninterruptable power supply, the system power
module for the system, or the service entrance transformer. If the building
has none of the above isolating units, the ground bar and the neutral bar
must be connected together in the service entrance power panel.
4.
Look inside all power panels to ensure the following:
Intermittent PIPs
Chapter 3. Problem Isolation Procedures (PIPs), Failing Items, and Symbolic FRU Isolation
335
Содержание i 830
Страница 1: ...iSeries iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts Version 5 SY44 5969 01...
Страница 2: ......
Страница 3: ...iSeries iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts Version 5 SY44 5969 01...
Страница 14: ...xii iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 15: ...Part 1 Problem Analysis Copyright IBM Corp 2000 2001 1...
Страница 16: ...2 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 628: ...Symbolic FRUs 614 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 629: ...Part 2 FRU Replacement Copyright IBM Corp 2000 2001 615...
Страница 630: ...616 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 817: ...Part Assemblies Chapter 5 Locations Addresses and Part Listings 803...
Страница 822: ...Assembly 2 continued 808 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 824: ...Assembly 2 continued 810 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 826: ...Assembly 2 continued 812 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 830: ...Assembly 3 continued 816 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 832: ...Assembly 3 continued 818 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 834: ...Assembly 3 continued 820 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 836: ...Assembly 3 continued 822 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 844: ...Assembly 6 continued 830 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 848: ...Assembly 7 continued 834 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 850: ...Assembly 7 continued 836 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 858: ...Assembly 10 continued 844 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 860: ...Assembly 10 continued 846 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 862: ...Assembly 10 continued 848 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 864: ...Assembly 10 continued 850 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 870: ...Assembly 12 continued 856 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 872: ...Assembly 12 continued 858 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 874: ...Assembly 12 continued 860 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 876: ...Assembly 12 continued 862 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 882: ...Assembly 14 continued 868 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 888: ...Assembly 16 continued 874 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 894: ...Assembly 19 External Cables External Cables 880 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 897: ...Miscellaneous Chapter 5 Locations Addresses and Part Listings 883...
Страница 898: ...Assembly 20 Miscellaneous Miscellaneous 884 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 906: ...892 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 962: ...948 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 963: ...Part 3 Appendixes Copyright IBM Corp 2000 2001 949...
Страница 964: ...950 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 968: ...954 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 970: ...956 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 974: ...960 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 980: ...966 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 982: ...968 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 984: ...970 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 986: ...972 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 990: ...976 iSeries Model 830 840 SB2 and SB3 Problem Analysis Repair and Parts V5R1...
Страница 999: ......
Страница 1000: ...Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber SY44 5969 01...