6-30
MM2 Motor Manager 2
GE Power Management
6.5 MEMORY MAP
6 COMMUNICATIONS
6
CONFIG.
INPUTS
con’t
44258
4257 10A1 Startup Override Delay
0-3601
1
s
F1*
0
44259
4258 10A2 Running Override Delay
0-3601
1
s
F1*
0
44260
4259 10A3 Operation
0-1
1
---
F18
0 = IL STOP
44261
4260 10A4 Instantaneous Alarm
0-1
1
---
F14
0 = DISABLE
44262
4261 10A5 ...Reserved...
...
...
...
...
...
44263
4262 10A6 ...Reserved...
...
...
...
...
...
44264
4263 10A7 ...Reserved...
...
...
...
...
...
44265
4264 10A8 Interlock Input 10 Function
0-34
1
---
F17
0 = NOT USED
44266
4265 10A9 Startup Override Delay
0-3601
1
s
F1*
0
44267
4266 10AA Running Override Delay
0-3601
1
s
F1*
0
44268
4267 10AB Operation
0-1
1
---
F18
0 = IL STOP
44269
4268 10AC Instantaneous Alarm
0-1
1
---
F14
0 = DISABLE
44270
4269 10AD Auto Mode Definition
0-1
1
---
F27
0 = SERIAL
44271
4270 10AE Local Isolator
0-1
1
---
F14
0 = DISABLE
44272
4271 10AF Auto Permissive Indication
0-1
1
---
F16
0 = MANUAL
PROCESS
INTER-
LOCK
NAMES
44273
4272 10B0 Process Intlk A Name chars 1 and 2
32-127
1
ASCII
F10
"PR"
44274
4273 10B1 Process Intlk A Name chars 3 and 4
32-127
1
ASCII
F10
"OC"
44275
4274 10B2 Process Intlk A Name chars 5 and 6
32-127
1
ASCII
F10
"ES"
44276
4275 10B3 Process Intlk A Name chars 7 & 8
32-127
1
ASCII
F10
"S "
44277
4276 10B4 Process Intlk A Name chars 9 & 10
32-127
1
ASCII
F10
"IN"
44278
4277 10B5 Process Intlk A Name chars 11 & 12 32-127
1
ASCII
F10
"TE"
44279
4278 10B6 Process Intlk A Name chars 13 & 14 32-127
1
ASCII
F10
"RL"
44280
4279 10B7 Process Intlk A Name chars 15 & 16 32-127
1
ASCII
F10
"OC"
44281
4280 10B8 Process Intlk A Name chars 17 & 18 32-127
1
ASCII
F10
"K "
44282
4281 10B9 Process Intlk A Name chars 19 & 20 32-127
1
ASCII
F10
"A "
44283
4282 10BA Serial Permissive
0-1
1
---
F14
0 = DISABLE
44284
4283 10BB Start Block Alarm
0-1
1
---
F14
0 = DISABLE
44285
4284 10BC Cmd mode change when running
0-1
1
---
F14
0 = DISABLE
44286
4285 10BD ...Reserved...
...
...
...
...
...
44287
4286 10BE ...Reserved...
...
...
...
...
...
44288
4287 10BF ...Reserved...
...
...
...
...
...
44289
4288 10C0 Process Intlk B Name chars 1 and 2
32-127
1
ASCII
F10
"PR"
44290
4289 10C1 Process Intlk B Name chars 3 and 4
32-127
1
ASCII
F10
"OC"
44291
4290 10C2 Process Intlk B Name chars 5 and 6
32-127
1
ASCII
F10
"ES"
44292
4291 10C3 Process Intlk B Name chars 7 and 8
32-127
1
ASCII
F10
"S "
Table 6–12: MODBUS MEMORY MAP (Sheet 11 of 21)
GROUP
MOD-
ICON
REGISTER
ADDRESS
DESCRIPTION
REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC
HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...