9-7
9 STARTER TYPES
9.3 TWO SPEED STARTER
9
9.3.2 MM2 SEQUENCES
START LOW SPEED sequence:
1. Start A command received by the MM2 (serial, switch input or faceplate).
2. Close and maintain Contactor A relay – the motor is now in low speed.
START DIRECTLY TO HIGH SPEED (motor stopped,
HIGH SPEED START BLOCK
not enabled)
sequence:
1. Start B command received by the MM2 (serial, switch input or faceplate).
2. Close and maintain Contactor B relay – the motor is now in high speed.
START DIRECTLY TO HIGH SPEED (motor stopped,
HIGH SPEED START BLOCK
enabled) sequence:
1. Start B command received by the MM2 (serial, switch input or faceplate).
2. No response to start B commands.
LOW TO HIGH SPEED TRANSITION sequence:
1. Start B command is received (serial, switch input or faceplate).
2. Open contactor A output relay.
3. Close and maintain Contactor B relay – the motor is now in high speed.
HIGH TO LOW SPEED TRANSITION sequence:
1. Start A command is received (serial, switch input or faceplate).
2. Open contactor B output relay.
3. Wait for the programmed transfer time.
4. Close and maintain contactor A.
STOP/TRIP sequence:
1. Stop command received by the MM2 or a trip occurs.
2. Open the currently closed contactor output relay.
There are many different configurations for the TWO SPEED starter type. Three of the more popular
ones are illustrated here: two-speed one winding constant or variable torque, two-speed one winding
constant horsepower, and two-speed two winding. See the two speed starter diagrams on the follow-
ing pages.
When the power to the MM2 is interrupted, all MM2 output relays de-energize, causing them to open
and stop the motor. The MM2 can only be wired for fail-safe operation.
If feedback is not received from the L or H contacts to the Contactor A or B Status N.O. input within
one second of closing Contactor A relay, an OPEN CONTROL CIRCUIT alarm will occur. This will
cause Contactor A and B output relays to open.
If feedback remains at the Contactor A or B Status N.O. input more than one second after opening
the Contactor A or B output relays, a WELDED CONTACTOR alarm will occur.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...