6-32
MM2 Motor Manager 2
GE Power Management
6.5 MEMORY MAP
6 COMMUNICATIONS
6
FIELD
STOP
44337
4336 10F0 Field Stop Mode
0-1
---
F19
0=Unlatched
44338
4337 10F1 ESD Stop Mode
0-1
---
F19
0=Unlatched
44339
4338 10F2 ESD Indication
0-1
---
F29
1=ON/Healthy
44340
4339 10F3 Faceplate Stop
0-1
---
F19
0=Unlatched
44341
4340 10F4 Process Stop
0-1
---
F19
0=Unlatched
44342
4341 10F5 ...Reserved...
...
...
...
...
...
44343
4342 10F6 ...Reserved...
...
...
...
...
...
44344
4343 10F7 ...Reserved...
...
...
...
...
...
ANALOG
INPUT
44345
4344 10F8 Analog Input Name chars 1 and 2
32-127
1
ASCII
F10
"AN"
44346
4345 10F9 Analog Input Name chars 3 and 4
32-127
1
ASCII
F10
"AL"
44347
4346 10FA Analog Input Name chars 5 and 6
32-127
1
ASCII
F10
"OG"
44348
4347 10FB Analog Input Name chars 7 and 8
32-127
1
ASCII
F10
" I"
44349
4348 10FC Analog Input Name chars 9 and 10
32-127
1
ASCII
F10
"NP"
44350
4349 10FD Analog Input Name chars 11 and 12
32-127
1
ASCII
F10
"UT"
44351
4350 10DE Analog Input Name chars 13 and 14
32-127
1
ASCII
F10
" "
44352
4351
10FF Analog Input Name chars 15 and 16
32-127
1
ASCII
F10
" "
44353
4352 1100 Analog Input Name chars 17 and 18
32-127
1
ASCII
F10
" "
44354
4353 1101 Analog Input Name chars 19 and 20
32-127
1
ASCII
F10
" "
44355
4354 1102 Analog Input Units chars 1 and 2
32-127
1
ASCII
F10
"UN"
44356
4355 1103 Analog Input Units chars 3 and 4
32-127
1
ASCII
F10
"IT"
44357
4356 1104 Analog Input Units chars 5 and 6
32-127
1
ASCII
F10
"S "
44358
4357 1105 Analog Input Units chars 7 and 8
32-127
1
ASCII
F10
44359
4358 1106 Analog Input Units chars 9 and 10
32-127
1
ASCII
F10
44360
4359 1107 Minimum Scale
0-20000
10
---
F1
0
44361
4360 1108 Maximum Scale
10-
20000
10
---
F1
1000
44362
4361 1109 Analog Alarm Low Level
1-20001
1
---
F1*
65535 = OFF
44363
4362 110A Analog Alarm Low Delay
1-600
1
s
F1
5
44364
4363 110B Analog Alarm High Level
1-20001
1
---
F1*
65535 = OFF
44365
4364 110C Analog Alarm High Delay
1-600
1
s
F1
5
44366
4365 110D Analog Trip Low Level
1-20001
1
---
F1*
65535 = OFF
44367
4366 110E Analog Trip Low Delay
1-600
1
s
F1
5
44368
4367 110F Analog Trip High Level
1-20001
1
---
F1*
65535 = OFF
44369
4368 1110 Analog Trip High Delay
1-600
1
s
F1
5
44370
4369 1111 Analog Low Override Delay
1-126
1
s
F1*
5
Table 6–12: MODBUS MEMORY MAP (Sheet 13 of 21)
GROUP
MOD-
ICON
REGISTER
ADDRESS
DESCRIPTION
REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC
HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...