GE Power Management
MM2 Motor Manager 2
4-21
4 SETPOINTS
4.4 S3 PROCESS
4
Interlock input functions are active when the applicable switch input is closed and
energized.
The MM2 has 10 programmable switch inputs. Each input can have one of many functions assigned
to it. Once a function is assigned to one Interlock input, that function cannot be assigned to any other
Interlock input. The Interlock functions are:
•
NOT USED: This is stored if this Interlock switch input is not used.
•
PROCESS INTERLOCK A-J: The Process Interlock functions are used to provide time depen-
dent trip / alarm / stop features based on a switch input. This function is used together with the
STARTUP OVERRIDE DELAY
,
RUNNING OVERRIDE DELAY
,
OPERATION
, and
INSTANTANEOUS ALARM
set-
points. The
STARTUP OVERRIDE
Delay
setpoint sets the amount of time that the Process Interlock
switch can remain open on the occurrence of a motor start. If the switch remains unhealthy for
longer than this time, a Process Interlock Trip or Process Interlock Stop will occur. If the Startup
Override Delay is set to 0 the Process Interlock switch must be healthy in order for the MM2 to
allow the motor to start. If the Startup Override Delay is set to OFF this timer is disabled. The
RUNNING OVERRIDE DELAY
setpoint sets the amount of time that the Process interlock switch can
be unhealthy during normal running. If the Process Interlock switch goes unhealthy after a motor
start and remains unhealthy for longer than the Running Override Delay, a Process Interlock Trip
or Process Interlock Stop will occur. If the
RUNNING OVERRIDE DELAY
is set to OFF, and the Pro-
cess Interlock switch goes unhealthy after the motor has started, no Process Interlock Trip or
Process Interlock Stop will occur. The
OPERATION
setpoint determines whether the Process Inter-
lock feature is a Process Interlock Trip (reset required in order to restart the motor) or a Process
Interlock Stop (no reset required). The
INSTANTANEOUS ALARM
setpoint is used to create an alarm
whenever the Process Interlock switch is unhealthy. There is no time delay associated with this
alarm feature. Note that the names of the Process Interlock features can be changed to any 20
alphanumeric character sequence. See
S3: PROCESS \ INTERLOCK NAMES
for further detail.
AUTO PERMISSIVE
INDICATION: MANUAL
Range: MANUAL, AUTO
AUTO MODE =
SERIAL
Range: SERIAL, HARD-WIRED
SERIAL PERMISSIVE:
DISABLE
Range: ENABLE, DISABLE
Allows serial commands to block all start commands (serial or manual)
until the unblock command is received. This setpoint must be enabled
before serial start block commands are executed. When set to
DISABLE
,
any start blocks in effect are automatically unblocked. The
START BLOCK
ALARM
setpoint can be used to indicate when a start was attempted
while a block was in effect.
START BLOCK ALARM:
DISABLE
Range: ENABLE, DISABLE
DISABLE COMMAND MODE
CHANGE WHEN RUNNING
Range: ENABLE, DISABLE
This setpoint allows the active command mode to be changed while the
motor is running. When set to
DISABLE
, the motor must first be stopped
before the command mode can be changed (Auto or Manual).
NOTE
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...