GE Power Management
MM2 Motor Manager 2
6-35
6 COMMUNICATIONS
6.5 MEMORY MAP
6
FLASH
MESSAGE
continued
44441
4440 1158 Flash message characters 33 and 34 32-255
1
ASCII
F10
" "
44442
4441 1159 Flash message characters 35 and 36 32-255
1
ASCII
F10
" "
44443
4442 115A Flash message characters 37 and 38 32-255
1
ASCII
F10
" "
44444
4443 115B Flash message characters 39 and 40 32-255
1
ASCII
F10
" "
44445
4444 115C ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44448
4447 115F ...Reserved...
...
...
...
...
...
COM-
MANDS
44449
4448 1160 Command Function Code
5
---
---
F1
5
44450
4449 1161 Command Operation Code
1-32
1
---
F22
0
44451
4450 1162 Command Data 1
0-65535
1
---
F1/F23/
F26
0
44452
4451 1163 Command Data 2
0-65535
1
---
F1
0
44453
4452 1164 Command Data 3
0-65535
1
---
F1
0
44454
4453 1165 Command Data 4
0-65535
1
---
F1
0
44455
4454 1166 Command Data 5
0-65535
1
---
F1
0
44456
4455 1167 Command Data 6
0-65535
1
---
F1
0
44457
4456 1168 Command Data 7
0-65535
1
---
F1
0
44458
4457 1169 Command Data 8
0-65535
1
---
F1
0
44459
4458 116A Command Data 9
0-65535
1
---
F1
0
44460
4459 116B Command Data 10
0-65535
1
---
F1
0
44461
4460 116C ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44464
4463 116F ...Reserved...
...
...
...
...
...
UNDER/
OVER
VOLTAGE
PROTEC-
TION
44465
4464 1170 Undervoltage Alarm Level
0-691
1
V
F1 *
691 = 0FF
44466
4465 1171 Undervoltage Alarm Delay
1-60
1
s
F1
10
44467
4466 1172 Undervoltage Trip Level
0-691
1
V
F1 *
691 = 0FF
44468
4467 1173 Undervoltage Trip Delay
1-60
1
s
F1
10
44469
4468 1174 Overvoltage Alarm Level
0-691
1
V
F1 *
691 = 0FF
44470
4469 1175 Overvoltage Alarm Delay
1-60
1
s
F1
10
44471
4470 1176 Overvoltage Trip Level
0-691
1
V
F1 *
691 = 0FF
44472
4471 1177 Overvoltage Trip Delay
1-60
1
s
F1
10
44473
4472 1178 ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44480
4479 117F ...Reserved...
...
...
...
...
...
Table 6–12: MODBUS MEMORY MAP (Sheet 16 of 21)
GROUP
MOD-
ICON
REGISTER
ADDRESS
DESCRIPTION
REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC
HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...