GE Power Management
MM2 Motor Manager 2
6-27
6 COMMUNICATIONS
6.5 MEMORY MAP
6
MOTOR
PROTEC-
TION
THERMAL
44153
4152 1038 Full Load Current
0-1000
1
**
F1
†
0 = OFF
44154
4153 1039 High Speed Full Load Current
5-1000
1
**
F1
100
44155
4154 103A Overload Curve Number
1-12
1
---
F1
4
44156
4155 103B Hot / Cold Curve Ratio
20-100
1
%
F1
75
44157
4156 103C Overload Pickup Level
100-125
1
0.01FLC
F1
100=1.00xFLC
44158
4157 103D ...Reserved...
...
...
...
...
...
44159
4158 103E ...Reserved...
...
...
...
...
...
44160
4159 103F ...Reserved...
...
...
...
...
...
MOTOR
PROTEC-
TION
GROUND
44161
4160 1040 Ground Fault Alarm Level (5 A CT)
3-101
1
% CT
F1*
65535 = OFF
44162
4161 1041 Gnd Fault Alarm Level (50:0.025 CT)
1-151
1
0.1 x A
F1*
65535 = OFF
44163
4162 1042 Ground Fault Alarm Delay on Run
1-60
1
s
F1
10
44164
4163 1043 Ground Fault Trip Level (residual)
3-101
1
% CT
F1*
65535 = OFF
44165
4164 1044 Gnd Fault Trip Level (50:0.025 CT)
0-151
1
0.1 x A
F1*
65535 = OFF
44166
4165 1045 Ground Fault Trip Delay on Run
0-100
1
0.1 x s
F1
10 = 1.0
44167
4166 1046 Delay Contactor GF Trip By (Aux1)
0-1000
100
ms
F1
0
44168
4167 1047 Delay Contactor GF Trip By (Aux2)
0-1000
100
ms
F1
0
44169
4168 1048 ...Reserved...
...
...
...
...
...
MOTOR
PROTECTI
ON
OPTIONS
44170
4169 1049 Minimize Reset Time
0-1
1
---
F14
1 = ENABLE
44171
4170 104A Stopped Motor Cooling Time
5-1080
1
minutes
F1
30
44172
4171 104B Overload Trip Reset
0-1
1
---
F16
0 = MANUAL
44173
4172 104C Phase Unbalance Alarm
0-1
1
---
F14
1 = ENABLE
44174
4173 104D Thermal Capacity Alarm
1-101
1
%
F1*
101 = OFF
44175
4174 104E Open Control Circuit Trip
0-1
1
---
F14
0 = Disable
44176
4175 104F Reset Alarms using the Reset Key
0-1
1
---
F14
0 = Disable
LOAD
PROTEC-
TION
44177
4176 1050 Under Power Alarm Level
2-11001
1
0.1 xkW
F1*
65535 = OFF
44178
4177 1051 Under Power Alarm Delay
1-60
1
s
F1
10
44179
4178 1052 Under Power Trip Level
2-11001
1
0.1 xkW
F1*
65535 = OFF
44180
4179 1053 Under Power Trip Delay
1-60
1
s
F1
10
44181
4180 1054 Acceleration Time Alarm Delay
5-1255
5
0.1 x s
F1*
65535 = OFF
44182
4181 1055 Acceleration Time Trip Delay
5-1255
5
0.1 x s
F1*
65535 = OFF
44183
4182 1056 Load Increase Alarm Level
20-111
1
% FLC
F1*
65535 = OFF
44184
4183 1057 Undercurrent Alarm Level
10-101
1
% FLC
F1*
65535 = OFF
44185
4184 1058 Undercurrent Alarm Delay
1-60
1
s
F1
10
44186
4185 1059 Undercurrent Trip Level
10-101
1
% FLC
F1*
65535 = OFF
44187
4186 105A Undercurrent Trip Delay
1-60
1
s
F1
10
Table 6–12: MODBUS MEMORY MAP (Sheet 8 of 21)
GROUP
MOD-
ICON
REGISTER
ADDRESS
DESCRIPTION
REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC
HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...