GE Power Management
MM2 Motor Manager 2
4-15
4 SETPOINTS
4.3 S2 PROTECTION
4
4.3.6 MOTOR PROTECTION – OPTIONS
PATH: SETPOINTS
tt
S2: PROTECTION
ttt
MOTOR PROTECTION OPTIONS
GROUND FAULT TRIP
DLY ON START: 1.0s
Range: 0.0 to 10.0 seconds; Step: 0.1 second
This delay is used when the motor is in a STARTING condition. If the
ground current is equal to or above the
GROUND PRIMARY TRIP PICKUP
setpoint value and remains this way for the time delay programmed in
this setpoint while the motor is starting, the assigned relay(s) will activate
and the
CAUSE OF TRIP: GROUND FAULT
message will be displayed.
When the phase current increases from 0, this delay is
used until the MM2 determines whether the motor is RUN-
NING or STARTING.
Refer to the
ACCELERATION TIME
setpoint in Section 4.3.7: LOAD PRO-
TECTION for details on how the MM2 detects a start condition.
MINIMIZE RESET TIME:
ENABLE
Range: ENABLE, DISABLE
The MM2 measures the motor thermal capacity used during a start.
This data can be used to minimize the lockout time following an Over-
load Trip. This allows the motor to be restarted after it has cooled to a
safe starting temperature. When set to
DISABLE
, the lockout time after
an Overload Trip will be the time required for the thermal memory to
reduce to 15%.
For example, if the thermal capacity used during the previous start is
40%, then after an occurrence of an Overload Trip, a RESET can be
accomplished when the thermal capacity decreases to 58% as shown:
100% – TC used during start – 2% Safety Margin
= 100% – 40% – 2% = 58%
STOPPED MOTOR COOL
TIME: 30 MINUTES
Range: 5 to 1080 minutes; Step: 1 minute
The
STOPPED MOTOR COOL TIME
determines how long it takes for a
stopped motor to reach steady state ambient temperature from its max-
imum allowable temperature. The maximum allowable temperature
occurs when the thermal capacity used reaches 100% (e.g. at the
occurrence of an Overload Trip). The Thermal Capacity value will
decrease exponentially to model the cooling characteristic of the motor.
The
STOPPED MOTOR COOL TIME
thus represents the time for the thermal
capacity value to decay through 5 time constants. Note that an Over-
load Trip can normally be reset when the thermal capacity value
decreases to 15%.
NOTE
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...