4-4
MM2 Motor Manager 2
GE Power Management
4.2 S1 CONFIGURATION
4 SETPOINTS
4
4.2.4 STARTER
PATH: SETPOINTS
t
S1: CONFIGURATION
ttt
STARTER
STARTER TYPE:
OFF
Range: OFF, FV NON-REVERSING, FV REVERSING, WYE DELTA
OPN TRANS, TWO SPEED, INVERTER, SLIP RING,
AUTOTRANS OPN TRANS, PART WINDING, WYE DELTA
CLS TRANS, AUTOTRANS CLS TRANS, DUTY/STANDBY,
SOFT STARTER, WYE DELTA OPN TRANS
Select a type according to the configuration that the MM2 is controlling.
This will determine the control logic used for Contactor A and Contactor
B start and stop sequences. See Chapter 9: STARTER TYPES for a
detailed description of each starter type.
CHANGE OVER CURRENT
1.5 xFLC
Range: 1.0 to 5.0 x FLC or OFF; Step: 0.1 x FLC
Appears only when
STARTER TYPE
is
WYE DELTA OPN TRNS
or
WYE DELTA
CLS TRANS
. Before
CHANGE OVER CURRENT
comes into effect on a wye
delta start, a minimum of 25% of the
CHANGE OVER TIME
must have
expired. After 25% of the time has expired and the average of the three
phase currents has dropped below the
CHANGE OVER CURRENT
value, the
transition from wye (Contactor A) to delta (Contactor B) will occur. If this
setpoint is
OFF
, 100% of the
CHANGE OVER TIME
must expire for the wye to
delta transition to occur.
CHANGE OVER TIME:
30 s
RANGE: 1 to 100 seconds; Step: 1 second
Appears only if
STARTER TYPE
is set as
WYE DELTA OPN TRNS
or
WYE DELTA
CLS TRANS
. See
CHANGE OVER CURRENT
setpoint above for operation.
TRANSFER TIME:
10 s
Range: 1 to 125 seconds; Step: 1 second
Appears only if
STARTER TYPE
is set as
FV REVERSING
or
TWO SPEED
. With
two-speed starters, this delay is required when the motor is switched
from high speed (Contactor B) to low speed (Contactor A). The delay
starts when Contactor B drops out. With a reversing starter, this delay
occurs when switching from forward (Contactor A) to reverse (Contactor
B) and from reverse to forward.
HIGH SPEED START
BLOCK: DISABLE
Range: ENABLE, DISABLE
Appears only if
STARTER TYPE
is
TWO SPEED
. When disabled, the MM2
allows the motor to be started directly to high speed. When enabled, the
motor must be started in low speed before switching to high speed.
RAMP UP TIME:
5 s
Range: 1 to 125 seconds; Step: 1 second
Appears only if
STARTER TYPE
is selected as
INVERTER
. See the descrip-
tion of the Inverter starter type for details on functionality.
RAMP DOWN TIME:
5 s
Range: 1 to 125 seconds; Step: 1 second
Appears only if
STARTER TYPE
is selected as
INVERTER
. See the descrip-
tion of the Inverter starter type for details on functionality.
STAGE ONE SHORTING
TIME: 5 s
Range: 1 to 125 seconds; Step: 1 second
Appears only if
STARTER TYPE
is
SLIP RING
or
PART WINDING
. This is the
time delay from the closure of Contactor A to the closure of Contactor B.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...