GE Power Management
MM2 Motor Manager 2
6-21
6 COMMUNICATIONS
6.5 MEMORY MAP
6
STATUS
continued
30033
32
0020 Speed Status Flags
---
---
---
F110
N/A
30034
33
0021 Cause of Stop
---
---
---
F5
N/A
30035
34
0022 Command Mode
---
---
---
F6
N/A
30036
35
0023 Motor Status
---
---
---
F7
N/A
30037
36
0024 Motor Mode
---
---
---
F8
N/A
30038
37
0025 Active Full Load Current
---
---
---
F1
N/A
30039
38
0026 Active Phase CT Primary
---
---
---
F1
N/A
30040
39
0027 Cause Of Duty Trip Alarm
---
---
---
F9
N/A
30041
40
0028 Cause of Last Stop
---
---
---
F5
N/A
30042
41
0029 Trip Type
F114
N/A
30043
42
002A Quick Status
F115
N/A
30044
43
002B ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
30048
47
002F ...Reserved...
...
...
...
...
...
MOTOR
DATA
30049
48
0030 Phase Current Scale Factor
---
---
---
F1
N/A
30050
49
0031 Phase A Current
---
---
**
F1
N/A
30051
50
0032 Phase B Current
---
---
**
F1
N/A
30052
51
0033 Phase C Current
---
---
**
F1
N/A
30053
52
0034 Ground Current
---
---
0.1 x A
F1
N/A
30054
53
0035 Motor Load
---
---
%FLC
F1
N/A
30055
54
0036 Thermal Capacity
---
---
%
F1
N/A
30056
55
0037 Current Unbalance
---
---
%
F1
N/A
30057
56
0038 Acceleration Time
---
---
0.1 x s
F1
N/A
30058
57
0039 Last Starting Current
---
---
**
F1
N/A
30059
58
003A O/L Time to Trip
---
---
s
F1
N/A
30060
59
003B Power - high order
---
---
0.1 x kW
F3
N/A
30061
60
003C Power - low order
---
---
0.1 x kW
F3
N/A
30062
61
003D Power (scaled)
---
---
kW
F21
N/A
30063
62
003E Energy Used - high order
---
---
0.1 xkWh
F2
N/A
30064
63
003F Energy Used - low order
---
---
0.1 xkWh
F2
N/A
30065
64
0040 Voltage
---
---
V
F1
N/A
30066
65
0041 ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
30072
71
0047 ...Reserved...
...
...
...
...
...
Table 6–12: MODBUS MEMORY MAP (Sheet 2 of 21)
GROUP
MOD-
ICON
REGISTER
ADDRESS
DESCRIPTION
REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC
HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...