GE Power Management
MM2 Motor Manager 2
4-27
4 SETPOINTS
4.4 S3 PROCESS
4
ANALOG TRIP LOW
OVERRIDE: 5 s
Range: 1 to 125 seconds or OFF; Step: 1
The analog level must reach a healthy state (greater than trip level)
after a start within the amount of time set by this setpoint. If the value is
0, the analog level must be healthy when a start is initiated or an analog
trip will occur immediately. If set to
OFF
, the trip will occur if the analog
level is unhealthy, regardless if the motor is running or stopped.
ANALOG TRIP LOW
DELAY: 5 s
Range: 1 to 600 seconds or OFF; Step: 1 second
The analog input scaled value must be below the
ANALOG TRIP LOW
LEVEL
for the time specified by this setpoint before a trip will occur.
ANALOG TRIP HIGH
LEVEL: OFF
Range: 1 to 20000 or OFF; Step: 1
If the analog input scaled value exceeds the level set by this setpoint,
an Analog Input High Trip will occur. Note that the trip level must be a
value between the
MINIMUM SCALE
and
MAXIMUM SCALE
values.
ANALOG TRIP HIGH
OVERRIDE: 5 s
Range: 1 to 125 seconds or OFF; Step: 1
The analog level must reach a healthy state (less than trip level) after a
start within the amount of time set by this setpoint. If the value is 0, the
analog level must be healthy when a start is initiated or an analog trip
will occur immediately. If the value is set to OFF, the trip will occur if the
analog level is unhealthy, regardless if the motor is running or stopped.
ANALOG TRIP HIGH
DELAY: 5 s
Range: 1 to 600 seconds or OFF; Step: 1 second
The analog input scaled value must be above the
ANALOG TRIP HIGH
LEVEL
for the time specified by this setpoint before a trip will occur.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...