6-26
MM2 Motor Manager 2
GE Power Management
6.5 MEMORY MAP
6 COMMUNICATIONS
6
STARTER
continued
44120
4119 1017 Changeover Time
1-125
1
s
F1
5
44121
4120 1018 Reserved
44122
4121 1019 Starts per Hour
1-41
1
s
F1*
5
44123
4122 101A High Speed Start Block
0-1
1
--
F14
0 = DISABLE
44124
4123 101B Contactor Sequence
0-1
1
--
F32
0 = 1S-2S
44125
4124 101C ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44128
4127 101F ...Reserved...
...
...
...
...
...
CT/VT
INPUTS
44129
4128 1020 Phase CT Primary
0-1000
5
A
F1
†
0 = OFF
44130
4129 1021 High Speed Phase CT Primary
5-1000
5
A
F1
100
44131
4130 1022 Ground CT Primary
5-1000
5
A
F1
100
44132
4131 1023 Ground Fault CT
0-2
1
---
F13
0=50:0.025
44133
4132 1024 VT Primary Voltage
110-601
1
---
F1*
601 = OFF
44134
4133 1025 VT Connection Type
0-1
1
---
F15
0=PHS (A-N)
44135
4134 1026 VT Secondary Voltage
110-120
10
V
F1
120
44136
4135 1027 Nominal Frequency
50-60
10
Hz
F1
60
THERMIS-
TOR
44137
4136 1028 Cold Resistance
1-300
1
0.1 x kW
F1
1 = 0.1 kW
44138
4137 1029 Hot Resistance
1-300
1
0.1 x kW
F1
50 = 5.0 kW
44139
4138 102A Thermistor Trip
0-1
1
---
F14
0 = DISABLE
44140
4139 102B Thermistor Alarm
0-1
1
---
F14
0 = DISABLE
44141
4140 102C ...Reserved...
...
...
...
...
...
44142
4141 102D ...Reserved...
...
...
...
...
...
44143
4142 102E ...Reserved...
...
...
...
...
...
44144
4143 102F ...Reserved...
...
...
...
...
...
FAULT
MODE
44145
4144 1030 Internal Fault Trip
0-1
1
---
F14
1 = ENABLE
44146
4145 1031 Serial Comms Failure Trip
5-30
5
---
F1*
30 = OFF
44147
4146 1032 Serial Comms Failure Alarm
5-30
5
---
F1*
30 = OFF
44148
4147 1033 Change command mode on Alarm
0-1
1
---
F14
0 = DISABLE
44149
4148 1034 ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44152
4151 1037 ...Reserved...
...
...
...
...
...
Table 6–12: MODBUS MEMORY MAP (Sheet 7 of 21)
GROUP
MOD-
ICON
REGISTER
ADDRESS
DESCRIPTION
REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC
HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...