GE Power Management
MM2 Motor Manager 2
4-31
4 SETPOINTS
4.5 S4 CONTROL
4
•
INTERLOCK 7:The AUX Relay 1 will energize while the Interlock 7 switch input is closed.
•
INTERLOCK 8: The AUX Relay 1 will energize while the Interlock 8 switch input is closed.
•
INTERLOCK 9: The AUX Relay 1 will energize while the Interlock 9 switch input is closed.
•
INTERLOCK 10: The AUX Relay 1 will energize while the Interlock 10 switch input is closed.
•
AUTO MODE: The AUX Relay 1 will energize when the AUTO LED is on.
•
MOTOR RUNNING: The AUX Relay 1 will energize while the motor is running in conjunction with
the Motor Start Delay and Motor Stop Delay.
•
GROUND FAULT TRIP: The AUX Relay 1 will energize when a ground fault trip occurs.
The MM2 energizes the auxiliary relay and de-energizes contactor A at the same
time the ground fault trip occurs. See the warning notes under Motor Protection/
Ground Fault for more details. Use the Delay Contactor Ground Fault Trip By set-
ting for coordination.
•
WYE DELTA CLS TRANS: This function must be configured when using the wye delta closed
transition starter type. See Section 9.11: WYE-DELTA CLOSED TRANSITION STARTER on
page 9–32 for more details.
•
AUTOTRANSFORMER 2S: This function must be configured when using the autotransformer
open/closed transition starter type. See Section 9.7: AUTOTRANSFORMER OPEN TRANSI-
TION STARTER on page 9–20 and 9.8: AUTOTRANSFORMER CLOSED TRANSITION
STARTER on page 9–24 for more details.
•
NOT USED: This function may be stored if the AUX Relay is not used. Factory default is serial
control.
•
SEGREGATED G/F ALARM: This function will energize the AUX Relay when a ground fault
alarm occurs. If the other AUX Relay is configured for ALARMS it will not operate until another
alarm occurs that is not a ground fault alarm.
•
THERMAL CAPACITY ALARM: The AUX Relay 1 will energize when a thermal capacity alarm
is present.
•
MOTOR AVAILABLE AUTO: This AUX Relay function will activate the AUX Relay when the
motor is available to start in Auto Mode.
•
MOTOR AVAILABLE: This AUX Relay function will activate the AUX Relay when the motor is
available to start regardless of which mode the MM2 is presently in (Auto or Manual). The AUX
Relay will remain active when the motor is running to indicate normal operation (that is, no stop
inputs or trips).
•
OVERLOAD: This AUX Relay function will activate the Aux Relay when the motor is tripped on
overload.
•
SOFT STARTER BYPASS: This AUX Relay function can be configured when using soft starter
type. See Section 9.13: SOFT STARTER on page 9–38 for more details.
WARNING
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...