GE Power Management
MM2 Motor Manager 2
10-1
10 CONTROL WIRE APPLICATIONS
10.1 TWO WIRE CONTROL
10
10 CONTROL WIRE APPLICATIONS
10.1 TWO WIRE CONTROL
10.1.1 DESCRIPTION
This control scheme is used when a maintained contact is in series with the starter coil. When the
PLC contact is closed the motor runs. When the PLC contact opens the motor stops.
To program the MM2 for two-wire control, set:
S3 PROCESS\PROGRAMMABLE INPUTS\INTERLOCK INPUT 1:
TWO WIRE CONTROL
S3 PROCESS\STOP CONFIGURATION\FACEPLATE STOP:
LATCHED
The
INTERLOCK INPUT 1
setpoint was chosen to match the wiring diagram provided. Any of
the available Interlocks 1 through 10 could be programmed for
TWO WIRE CONTROL
.
10.1.2 CONTROL OPERATION
START:
•
Start command received (switch input) and maintained.
STOP:
•
Start command removed.
•
Pressing the STOP key causes a latched trip. The motor cannot be restarted until the RESET
key is pressed.
Terminal 11 (Stop input) must be closed to allow a start. The MM2 display will read “Motor Status
Unavailable” when the stop input is open.
If feedback is not received by the Contactor A relay Status N.O. inputs within 1 second of closing
Contactor A output relay, an OPEN CONTROL CIRCUIT alarm will occur. This will cause Contactor
A output relay to open.
NOTE
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...