9 STARTER TYPES
9.7 AUTOTRANSFORMER OPEN TRANSITION STARTER
9
S3 PROCESS\PROGRAMMABLE INPUTS\INTERLOCK INPUT 10:
AUTOTRANS 2S CONTACT
S4 CONTROL\AUX 1 RELAY CONFIG\AUX RELAY 1 FUNCTION:
AUTOTRANSFORMER 2S
The
CONTACTOR SEQUENCE
setpoint appears when
STARTER TYPE
is selected as
AUTOTRANS OPN
TRANS
. The
1S-2S
value closes the 1S contactor ahead of the 2S contactor as per some manufac-
turer’s wiring practices. The
2S-1S
value closes the 2S contactor ahead of the 1S contactor, another
common wiring practice.
The
CHANGE OVER TIME
setpoint appears when
STARTER TYPE
is selected as
AUTOTRANS OPN TRANS
.
This represents the time delay from the closure of Contactor A until the opening of Contactor A.
The
STARTS PER HOUR
setpoint appears only when
STARTER TYPE
is selected as
AUTOTRANS OPN
TRANS
. This setpoint limits the number of starts per hour to prevent overheating of the autotrans-
former windings.
9.7.2 MM2 SEQUENCES
START (
CONTACTOR SEQUENCE
set to
1S-2S
) sequence:
1. Start command received by the MM2 (serial, switch input or faceplate).
2. Close and maintain Contactor A output relay – close 1S contactor.
3. Wait 20 ms, close and maintain Aux. 1 output relay – power is applied to the autotransformer.
4. Wait for the time set in the
CHANGE OVER TIME
setpoint.
5. Open Contactor A and Aux. output relays.
6. Wait 20 ms.
7. Close and maintain Contactor B output relay.
START (
CONTACTOR SEQUENCE
set to
2S-1S
) sequence:
1. Start command received by the MM2 (serial, switch input or faceplate).
2. Close and maintain Aux. 1 output relay – power is applied to the autotransformer.
3. Wait 20 ms, close and maintain Contactor A output relay – close the 1S contactor.
4. Wait for the time set in the CHANGE OVER TIME setpoint.
5. Open Contactor A and Aux. output relays.
6. Wait 20 ms.
7. Close and maintain Contactor B output relay.
STOP/TRIP sequence:
1. Stop command received by the MM2 or a trip occurs.
2. Open Contactor B output relay.
If feedback is not received from the 1S, 2S or R contacts to the Contactor A, B or auxiliary relay Sta-
tus N.O. inputs within one second of closing Contactors A, B or the auxiliary relay, an OPEN CON-
TROL CIRCUIT alarm will occur. This will cause Contactors A, B and the auxiliary relay to open.
If feedback remains at any of the Status N.O. inputs for more than one second after opening the its
respective relay, a WELDED CONTACTOR alarm will occur.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...