9-30
MM2 Motor Manager 2
GE Power Management
9.10 WYE-DELTA OPEN TRANSITION STARTER
9 STARTER TYPES
9
9.10.2 MM2 SEQUENCES
START sequence:
1. Start command received by the MM2 (serial, switch input or faceplate).
2. Close Contactor A output relay – the motor is now in a wye configuration.
3. Close Aux. output relay 1M contact.
4. Maintain 1S contactor until
CHANGE OVER CURRENT
or
CHANGE OVER TIME
initiates a transition from
wye to delta. See
CHANGE OVER CURRENT
and
CHANGE OVER TIME
descriptions above for more
detail.
5. Open Contactor A output relay – change over delay 20 ms wye to delta.
6. Close and maintain Contactor B output relay – the motor is now in a delta configuration.
STOP/TRIP sequence:
1. Stop command received by the MM2 or a trip occurs.
2. Open contactor B output relay.
3. Open Aux. output relay 1M contact
When the power to the MM2 is interrupted, all output relays on the MM2 will de-energize causing
them to open and stop the motor. The MM2 can only be wired for fail-safe operation.
If feedback is not received from the Contactor A Status N.O. input within one second of closing Con-
tactor A relay, an OPEN CONTROL CIRCUIT alarm will occur. This will cause All starter output
relays to open. If feedback remains at the Contactor A Status N.O. input more than one second after
opening the Contactor A output relay, a WELDED CONTACTOR alarm will occur.
If feedback is not received from the Contactor B Status N.O. input within one second of closing Con-
tactor B relay, an OPEN CONTROL CIRCUIT alarm will occur. This will cause All starter output
relays to open. If feedback remains at the Contactor B Status N.O. input more than one second after
opening the Contactor B output relay, a WELDED CONTACTOR alarm will occur.
If feedback is not received from the Wye Delta 1M contact interlock input within one second of clos-
ing Contactor A relay, an OPEN CONTROL CIRCUIT alarm will occur. This will cause All starter out-
put relays to open. If feedback remains at the Wye Delta 1M contact interlock input more than one
second after opening the AUX. output relay, a WELDED CONTACTOR alarm will occur.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...