GE Power Management
MM2 Motor Manager 2
9-17
9 STARTER TYPES
9.6 INVERTER STARTER
9
9.6 INVERTER STARTER
9.6.1 DESCRIPTION
When the RUN contact closes the inverter ramps up the motor to the programmed speed. When the
RUN contact opens, the inverter ramps down the motor to a stop.
Figure 9–13: ELEMENTARY INVERTER STARTER
To program the MM2 for inverter starter, set:
S1 CONFIGURATION\STARTER\STARTER TYPE:
INVERTER
S1 CONFIGURATION\STARTER\RAMP UP TIME:
1 to 125 sec.
S1 CONFIGURATION\STARTER\RAMP DOWN TIME:
1 to 125 sec.
The
RAMP UP TIME
and
RAMP DOWN TIME
setpoints appear when the
STARTER TYPE
is selected as
INVERTER
. See the next section for details on functionality.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...