GE Power Management
MM2 Motor Manager 2
4-33
4 SETPOINTS
4.6 S5 MONITORING
4
4.6.3 PRESET COUNTERS AND TIMERS
PATH: SETPOINTS
ttttt
S5 MONITORING
tt
PRESET COUNTERS AND TIMERS
PRESET RUNNING HOURS:
0
HRS
Range: 0 to 65535; Step 1
Sets the number of Running Hours to a predetermined value.
PRESET STOPPED HOURS:
0
HRS
Range: 0 to 65535; Step 1
Sets the number of Stopped Hours to a predetermined value.
PRESET NUMBER OF
STARTS:
X100
Range: 0 to 65535; Step 1
Sets the Number Of Starts to a predetermined value within 100 starts.
PRESET OVERLOAD
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Overload Trips to a predetermined value.
PRESET THERMISTOR
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Thermistor Trips to a predetermined value.
PRESET GROUND FAULT
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Ground Fault trips to a predetermined value.
PRESET SINGLE PHASE
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Single Phase trips to a predetermined value.
PRESET ACCELERATION
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Acceleration trips to a predetermined value.
PRESET UNDERCURRENT
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Undercurrent trips to a predetermined value.
PRESET UNDERPOWER
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Underpower trips to a predetermined value.
PRESET STALLED ROTOR
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Stalled Rotor trips to a predetermined value.
PRESET STALLED ROTOR
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Stalled Rotor trips to a predetermined value.
PRESET CONTROL
TRIPS: 0
Range: 0 to 65535; Step 1
Sets the number of Control trips to a predetermined value.
PRESET INTERLOCK
COUNTER: 0
Range: 0 to 65535; Step 1
Sets the number of Interlock Counter operations to a predetermined
value.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...