GE Power Management
MM2 Motor Manager 2
4-19
4 SETPOINTS
4.3 S2 PROTECTION
4
4.3.8 UNDER/OVERVOLTAGE PROTECTION
PATH: SETPOINTS
tt
S2: PROTECTION
ttttt
UNDER/OVERVOLTAGE PROTECTION
UNDERVOLTAGE ALARM
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. This feature functions
the same as the Undervoltage Trip feature but produces an alarm indi-
cation instead of a trip.
UNDERVOLTAGE ALARM
DELAY: 10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Enter the delay for acti-
vation of the Undervoltage Alarm.
UNDERVOLTAGE TRIP
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. If the voltage remains
below this value while the motor is running for the time specified in the
UNDERVOLTAGE TRIP DELAY
, the MM2 will trip. Set this value to
OFF
if no
Undervoltage Trip is required.
UNDERVOLTAGE TRIP
DELAY: 10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Set the
UNDERVOLTAGE
TRIP DELAY
long enough to prevent nuisance trips from momentary volt-
age dips when the Undervoltage Trip feature is used.
OVERVOLTAGE ALARM
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. This feature functions
the same as the Overvoltage Trip feature but produces an alarm indica-
tion instead of a trip.
OVERVOLTAGE ALARM
DELAY:
10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Enter the delay for acti-
vation of the Overvoltage Alarm.
OVERVOLTAGE TRIP
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. If the voltage remains
above this value while the motor is running for the time specified in the
OVERVOLTAGE TRIP DELAY
, the MM2 will trip. Set this value to
OFF
if no
Overvoltage Trip is required.
OVERVOLTAGE TRIP
DELAY:
10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Set the
OVERVOLTAGE
TRIP DELAY
long enough to prevent nuisance trips from momentary volt-
age dips when the Undervoltage Trip feature is used.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...