6
6.6 DATA FORMATS
6.6.1 DATA FORMATS TABLE
Table 6–13: DATA FORMATS (Sheet 1 of 15)
CODE
DESCRIPTION
BITMASK
F1
Unsigned Integer: Numerical Data
FFFF
F2
Unsigned Long Int: Numerical Data
FFFFFFFF
F3
Signed Long Integer: Numerical Data
FFFFFFFF
F4
Hardware Version Code
---
1 = A
---
↓
↓
26 = Z
---
F5
Unsigned Integer: Cause of Stop
FFFF
0 = No Stop
---
1 = Process Interlock A Stop
---
2 = Process Interlock B Stop
---
3 = Process Interlock C Stop
---
4 = Process Interlock D Stop
---
5 = External Stop
---
6 = ESD Stop
---
7 = Process Interlock E Stop
---
8 = Process Interlock F Stop
---
9 = Process Interlock G Stop
---
10 = Process Interlock H Stop
---
11 = Process Interlock I Stop
---
12 = Process Interlock J Stop
---
13 = Faceplate Stop
---
14 = Process Stop
---
15 = Serial Stop
---
16 = Two-Wire Stop
---
17 = Stop A Interlock Stop
---
18 = Stop B Interlock Stop
---
F6
Unsigned Integer: Command Mode
FFFF
0 = Manual
---
1 = Auto
---
2 = Manual Inhibit
---
3 = Manual and Auto
---
4 = Hard-Wire Auto
---
F7
Unsigned Integer - Drive Status
FFFF
0 = Unavailable
---
1 = Available - Auto
---
2 = Available - Manual
---
3 = Available (Manual & Auto)
---
4 = Running
---
5 = ESD TRIP or STOP (Mod)
F8
Unsigned Integer: Motor Mode
FFFF
0 = Starting
---
1 = Stopped
---
2 = Running
---
F9
Unsigned Integer - Cause of Trip
FFFF
0 = No Trip
---
1 = Process Interlock A
---
2 = Process Interlock B
---
3 = Process Interlock C
---
4 = Process Interlock D
---
5 = Parameters Not Set
---
6 = Faceplate Stop
---
7 = Process Stop
---
11 = Overload
---
12 = Single Phase
---
13 = Thermistor
---
14 = Acceleration Time
---
15 = Ground Fault
---
16 = Stalled Rotor
---
17 = Not Used
---
18 = Local Isolator
---
19 = Serial Communications Failure
---
20 = Internal Fault
---
21 = Undercurrent
---
22 = Emergency Stop
---
23 = Underpower
---
24 = Analog Input High
---
25 = Analog Input Low
---
26 = Plant Interlock
---
27 = Process Interlock E
---
Table 6–13: DATA FORMATS (Sheet 2 of 15)
CODE
DESCRIPTION
BITMASK
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...