5.2 A1 DATA
5 ACTUAL VALUES
5
5.2.3 PROCESS DATA
PATH: ACTUAL VALUES
t
A1: DATA
tt
PROCESS DATA:
5.2.4 PROGRAMMABLE MESSAGE
PATH: ACTUAL VALUES
t
A1: DATA
ttt
PROGRAMMABLE MESSAGE:
THERMAL CAPACITY
USED = 21 %
This message displays the thermal memory accumulated according to
motor
I
2
t history and chosen overload curve. A thermal capacity value
equal to 100% causes an Overload Trip.
PHASE CURRENT
UNBALANCE =
1 %
Displays the percentage unbalance in the motor phase currents. The
unbalance is calculated as shown in Section 1.2.1: MM2 SPECIFICA-
TIONS on page 1–4.
ACCELERATION TIME =
0.0 s
This message displays the motor acceleration time from the last motor
start. This value is determined by the amount of time required for the
average phase current to go below 1.0
×
FULL LOAD CURRENT
after a
motor start.
LAST STARTING
CURRENT = 340 AMPS
This message displays the maximum current measured during the last
motor start. This value is saved until the next start or until power is
cycled on the MM2.
O/L TIME TO TRIP =
---- s
This message displays the estimated time to trip based on the present
overload level and thermal capacity used. This message is only used in
conjunction with overload trips.
POWER =
+1000 kW
This message displays the three phase power, calculated using phase
A current and voltage
V
an
or
V
ab
. This message will appear only if the
VT PRIMARY VOLTAGE
setpoint is programmed.
ENERGY USED =
10600 kWhr
This message displays the total accumulated energy used since last
cleared. This value is updated once every minute. This message will
appear only if the
VT PRIMARY VOLTAGE
setpoint is programmed.
VT VOLTAGE =
480 V
This message displays the voltage present at the primary of the VT.
This message will appear only if the
VT PRIMARY VOLTAGE
setpoint is pro-
grammed.
ANALOG INPUT=
142 UNITS
This message displays the 4 to 20 mA analog input value scaled to the
minimum and maximum values as specified in setpoints. The analog
input name and units are user definable in the setpoints area of the
MM2 messages.
PROGRAMMABLE MESSAGE
SAMPLE TEXT
This message displays the 4 to 20 mA analog input value scaled to the
minimum and maximum values as specified in setpoints. The analog
input name and units are user definable in the setpoints area of the
MM2 messages.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...