4-6
MM2 Motor Manager 2
GE Power Management
4.2 S1 CONFIGURATION
4 SETPOINTS
4
4.2.6 THERMISTOR
PATH: SETPOINTS
t
S1: CONFIGURATION
ttttt
THERMISTOR
4.2.7 FAULT MODE
PATH: SETPOINTS
t
S1: CONFIGURATION
tttttt
FAULT MODE
COLD RESISTANCE:
0.1 kOHMS
Range: 0.1 to 30.0 kOHMS; Step: 0.1
For a PTC thermistor, enter the resistance that the thermistor must drop
below before a Thermistor Trip or Alarm can be cleared. For a NTC ther-
mistor, enter the resistance that the thermistor must rise above before a
Thermistor Trip or Alarm can be cleared.
HOT RESISTANCE
5.0 kOHMS
Range: 0.1 to 30.0 kOhms, STEP: 0.1
For a PTC thermistor, enter the resistance that the thermistor must rise
above before a Thermistor Trip or Alarm will occur. For a NTC ther-
mistor, enter the resistance that the thermistor must drop below before a
Thermistor Trip or Alarm will occur.
THERMISTOR TRIP:
DISABLE
Range: ENABLE, DISABLE
When a thermistor is used, it can be selected for an Alarm or Trip or
both. Choose
ENABLE
to allow Thermistor Trips to occur.
THERMISTOR ALARM:
DISABLE
Range: ENABLE, DISABLE
When a thermistor is used, it can be selected for an Alarm or Trip or
both. Choose
ENABLE
to allow Thermistor Alarms to occur.
INTERNAL FAULT TRIP
ENABLE
Range: ENABLE, DISABLE
An internal fault during self-checking will cause an alarm. Since opera-
tion may be erratic depending on the fault condition, it may be desirable
to trip the motor by setting this setpoint to
ENABLE
. The MM2 continues to
run the motor with an internal fault present if set to
DISABLE
.
SERIAL COMM FAILURE
TRIP: OFF s
Range: 5 to 25 seconds or OFF; Step: 5 seconds
If using serial communications to control a process with several motors
working together, it may be desirable to shut down the motor if commu-
nication control is lost. When no activity occurs on the communications
port for 5 to 25 seconds, it will trip if this feature is enabled.
SERIAL COMM FAILURE
ALARM: OFF
Range: 5 to 25 seconds or OFF; Step: 5 seconds
Sets an alarm when the serial communication link is interrupted.
CHANGE COMMAND MODE
ON ALARM: DISABLE
Range: ENABLE, DISABLE
Allows the command mode to automatically switch from AUTO to MAN-
UAL when the
SERIAL COMMS FAILURE ALARM
is active. If the motor was
running when the alarm occurred it will be stopped and will restart based
on manual start inputs only. When serial communication is restored the
MM2 will remain in MANUAL command mode.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...