9-36
MM2 Motor Manager 2
GE Power Management
9.12 DUTY/STANDBY STARTER
9 STARTER TYPES
9
9.12.3 NOTES
When the power to the MM2 is interrupted, all output relays on the MM2 will de-energize causing
them to open and stop the motor. The MM2 can only be wired for fail-safe operation.
If feedback is not received by the Contactor A Status N.O. or Contactor B Status N.O. inputs within
one second of closing the corresponding output relay, an OPEN CONTROL CIRCUIT alarm will
occur. This will open the active output relay which will stop the motor.
If feedback remains at Contactor A Status N.O. or Contactor B Status N.O. inputs for more than one
second after opening the corresponding output relay, a WELDED CONTACTOR alarm will occur.
The Start A input and key are used to start motors A and B. The Start B input and faceplate key have
no effect.
Serial Control starts override the mode of operation of the Duty/Standby starter. For example a serial
start B command will always start motor B and a serial start A will always start motor A. This is true
for AUTO START A and AUTO START B programmable interlock functions as well.
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...