6-42
MM2 Motor Manager 2
GE Power Management
6.6 DATA FORMATS
6 COMMUNICATIONS
6
F9
con’t
28 = Process Interlock F
---
29 = Process Interlock G
---
30 = Process Interlock H
---
31 = Process Interlock I
---
32 = Process Interlock J
---
F10
Two ASCII Characters
FFFF
32 to 127 = ASCII Character
7F00
32 to 127 = ASCII Character
007F
F11
Unsigned Integer: Starter Type
FFFF
0 = Off
---
1=Full Voltage (Direct On Line)
Non-Reversing
---
2 = Full Voltage (Direct On Line)
Reversing
---
3 = Wye-Delta Open Transition
---
4 = Two Speed
---
5 = Inverter
---
6 = Slip Ring
---
7 = Autotransformer Open Transition
---
8 = Part Winding
---
9 = Wye Delta Closed Transition
---
10 = Autotransformer Closed
Transition
---
11 = Duty/Standby
---
12 = Soft Starter
---
F12
Unsigned Integer: AUX Relay
Operation
FFFF
0 = Non-Failsafe
1 = Failsafe
F13
Unsigned Integer - Ground CT Type
FFFF
0 = 50:0.025 CBCT
---
1 = 5A Secondary CBCT
---
2 = Residual
---
F14
Unsigned Integer: Enable/Disable
FFFF
0 = Disable
---
1 = Enable
---
F15
Unsigned Integer: VT Connection Type
FFFF
0 = Line (A-B)
---
1 = Phase (A-N)
---
F16
Unsigned Integer: Manual/Auto
FFFF
0 = Manual
---
1 = Auto
---
Table 6–13: DATA FORMATS (Sheet 3 of 15)
CODE
DESCRIPTION
BITMASK
F17
Interlock Input function
FFFF
0 = Not Used
---
1 = Process Interlock A
---
2 = Process Interlock B
---
3 = Process Interlock C
---
4 = Process Interlock D
---
5 = Plant Interlock
---
6 = Lockout Reset
---
7 = Setpoint Access
---
8 = Auto Permissive
---
9 = Auto Start A
---
10 = Auto Start B
---
11 = Reset Emergency Stop Trip
---
12 = Reset Undercurrent Trip
---
13 = Two Wire Control
---
14 = Test Switch
---
15 = Remote Permissive
---
16 = Communication Select
---
17 = Interlock Counter
---
18 = AUX Relay 1 Inhibit
---
19 = Wye Delta 1M Contact
---
20 = Wye Delta 2S Contact
---
21 = U/V Restart Inhibit
---
22 = Autotransformer 2S Contact
---
23 = Process Interlock E
---
24 = Process Interlock F
---
25 = Process Interlock G
---
26 = Process Interlock H
---
27 = Process Interlock I
---
28 = Process Interlock J
---
29 = Stop A
---
30 = Stop B
---
31 = Remote Reset
---
32 = Motor Selector A/B
---
33 = Duty Select Man/Auto
---
34 = Bypass Contact
---
F18
Unsigned Integer:
Interlock Stop / Latched Trip
FFFF
0 = Interlock Stop
---
1 = Latched Trip
---
Table 6–13: DATA FORMATS (Sheet 4 of 15)
CODE
DESCRIPTION
BITMASK
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...