GE Power Management
MM2 Motor Manager 2
1-5
1 INTRODUCTION
1.3 SPECIFICATIONS
1
CALCULATION METHOD: if
I
AV
≥
I
FLC
:
if
I
AV
<
I
FLC
:
where
I
AV
= average phase current
I
M
= current in a phase with maximum deviation from
I
AV
I
FLC
=
MOTOR FULL LOAD CURRENT
setpoint
THERMAL COOLING TIMES
RANGE:
5 to 1080 min when motor is stopped;
50% of motor stopped value when motor is running.
ACCURACY:
± 1 minute
UNDERCURRENT
RANGE:
10 to 100%
×
motor FLC or OFF
DELAY RANGE:
1 to 60 seconds
ACCURACY:
±1 second
STALLED ROTOR
RANGE:
1.15 to 4.50
×
FLC or OFF
DELAY RANGE:
0.5 to 5 seconds
ACCURACY:
±0.5 second
THERMISTOR INPUTS
SENSOR TYPES:
positive temperature coefficient PTC;
R
HOT
=100 to 30000
Ω
negative temperature coefficient NTC;
R
HOT
=100 to 30000
Ω
DELAY:
1 second
ACCURACY:
±5% or 100
Ω
(whichever is greater)
ANALOG INPUT
RANGE:
4 to 20 mA
ACCURACY:
±1% of full scale
ALARM:
programmable 4 to 20 mA
TRIP:
programmable 4 to 20 mA
COMMUNICATIONS
TYPE:
RS485 2 wire, half duplex
BAUD RATE:
1200 to 19200 baud
PROTOCOL: Modbus
RTU
FUNCTIONS:
Read/write setpoints, Read coil status, Read actual values, Read device status,
Execute commands, Loopback Test
UB%
I
M
I
AV
–
i
AV
----------------------
100%
×
=
UB%
I
M
I
AV
–
i
AV
----------------------
100%
×
=
Содержание MOTOR MANAGER 2
Страница 2: ......
Страница 4: ......
Страница 21: ...GE Power Management MM2 Motor Manager 2 2 3 2 INSTALLATION 2 1 MOUNTING 2 Figure 2 4 TYPICAL WIRING DIAGRAM ...
Страница 33: ...GE Power Management MM2 Motor Manager 2 3 7 3 HARDWARE 3 3 THEORY OF OPERATION 3 Figure 3 2 BLOCK DIAGRAM ...
Страница 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Страница 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Страница 130: ...7 2 MM2 Motor Manager 2 GE Power Management 7 1 INJECTION TESTING 7 TESTING 7 Figure 7 1 SECONDARY INJECTION TEST SETUP ...
Страница 153: ...GE Power Management MM2 Motor Manager 2 9 5 9 STARTER TYPES 9 2 FV REVERSING STARTER 9 Figure 9 4 FV REVERSING STARTER ...
Страница 161: ...GE Power Management MM2 Motor Manager 2 9 13 9 STARTER TYPES 9 4 SLIP RING STARTER 9 Figure 9 10 SLIP RING STARTER ...
Страница 187: ...GE Power Management MM2 Motor Manager 2 9 39 9 STARTER TYPES 9 13 SOFT STARTER 9 Figure 9 25 SOFT STARTER ...
Страница 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Страница 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Страница 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...